Parameter Locations, Descriptions, and Default Values
PARAMETER NAME/ | DESCRIPTION | DISPLAY SCREENS / | |
[MENU LOCATION] |
| DEFAULT SETTINGS | |
|
|
| |
System Temperature | System temperature measured within the | Sys Temp | + |
{Status Only} | control unit. | 26.7 | C |
[STATUS] |
|
|
|
System Voltage | System output voltage measured | Sys Voltage | + |
{Status Only} | between the power plant +24V and | 27.00 V | |
[STATUS] | return buses. |
|
|
Test Major Relay | Setting this parameter to “ON” de- | Test Maj Rly | m+ |
Security Level {1} | energizes the Major Relay and turns on | OFF |
|
[SYSTEM/DIAG] | the “MAJ” LED on the control unit front |
|
|
| panel. In normal operation Major Relay |
|
|
| is energized so that when a loss of +24 |
|
|
| Vdc power occurs, the relay will change |
|
|
| state. |
|
|
Test Minor Relay | Setting this parameter to “ON” energizes | Test Min Rly | m+ |
Security Level {1} | the Minor Relay and turns on the “MIN” | OFF |
|
[SYSTEM/DIAG] | LED on the control unit front panel. |
|
|
Test Relay 1 | Setting this parameter to “ON” energizes | Test Relay 1 | m+ |
Security Level {1} | Relay 1 and turns on the “ALM1” LED on | OFF |
|
[SYSTEM/DIAG] | the control unit front panel. |
|
|
• | • | • |
|
• | • |
| |
• |
| ||
• | • |
| |
Test Relay 6 | Setting this parameter to “ON” energizes | • |
|
Security Level {1} | Relay 6 and turns on the “ALM6” LED on | Test Relay 6 | m+ |
[SYSTEM/DIAG] | the control unit front panel. | OFF |
|
|
|
| |
|
|
| |
Test Relay Enable | This parameter must be set to “Enable” | Test Relay En m+ | |
Security Level {1} | to permit the eight output relays to be | Disable |
|
[SYSTEM/DIAG] | manually tested; otherwise, the state of |
|
|
| the relays will be per system conditions. |
|
|
Time | Internal system clock time | Time | m+ |
Security Level {1} | format). Used as a date stamp in the | 9:00:25 |
|
[SYSTEM/DATE] | event log. |
|
|
MX28B400 +24 VDC User’s Manual | Page 33 |