Parameter Locations, Descriptions, and Default Values

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

System Temperature

System temperature measured within the

Sys Temp

+

{Status Only}

control unit.

26.7

C

[STATUS]

 

 

 

System Voltage

System output voltage measured

Sys Voltage

+

{Status Only}

between the power plant +24V and

27.00 V

[STATUS]

return buses.

 

 

Test Major Relay

Setting this parameter to “ON” de-

Test Maj Rly

m+

Security Level {1}

energizes the Major Relay and turns on

OFF

 

[SYSTEM/DIAG]

the “MAJ” LED on the control unit front

 

 

 

panel. In normal operation Major Relay

 

 

 

is energized so that when a loss of +24

 

 

 

Vdc power occurs, the relay will change

 

 

 

state.

 

 

Test Minor Relay

Setting this parameter to “ON” energizes

Test Min Rly

m+

Security Level {1}

the Minor Relay and turns on the “MIN”

OFF

 

[SYSTEM/DIAG]

LED on the control unit front panel.

 

 

Test Relay 1

Setting this parameter to “ON” energizes

Test Relay 1

m+

Security Level {1}

Relay 1 and turns on the “ALM1” LED on

OFF

 

[SYSTEM/DIAG]

the control unit front panel.

 

 

 

 

 

 

Test Relay 6

Setting this parameter to “ON” energizes

 

Security Level {1}

Relay 6 and turns on the “ALM6” LED on

Test Relay 6

m+

[SYSTEM/DIAG]

the control unit front panel.

OFF

 

 

 

 

 

 

 

Test Relay Enable

This parameter must be set to “Enable”

Test Relay En m+

Security Level {1}

to permit the eight output relays to be

Disable

 

[SYSTEM/DIAG]

manually tested; otherwise, the state of

 

 

 

the relays will be per system conditions.

 

 

Time

Internal system clock time (24-hour

Time

m+

Security Level {1}

format). Used as a date stamp in the

9:00:25

 

[SYSTEM/DATE]

event log.

 

 

MX28B400 +24 VDC User’s Manual

Page 33

Page 37
Image 37
American Power Conversion MX28B400 Sys Temp, 26.7, Sys Voltage, Test Maj Rly, Test Min Rly, Test Relay En m+, Time