Guardian Technologies 4582 & 4987 Test 31 Remove Wire 18 / Shutdown Lead, Refer to Flow Chart

Models: 5308 4583 4451 & 4986 4582 & 4987

1 90
Download 90 pages 17.81 Kb
Page 56
Image 56

Section 6

DIAGNOSTIC TESTS

TEST 31 - Remove Wire 18 / Shutdown

Lead

PROCEDURE:

leads across TEST POINTS B INFINITY should be measured. Connect meter test leads across TEST POINTS C. INFINITY should be measured (See Figure 6-42). If the SSR fails any test replace it.

1.Disconnect Wire 18 from the Stud located above the oil cooler that extends out From the shrouding.

2.Perform Test 29 again checking for Spark.

RESULTS:

Refer back to Flow Chart.

WIRE 18

SHUTDOWN

LEAD

Figure 6-40. – Wire 18

6.Remove Wire 229 from the SSR. Connect a jumper lead from the terminal of the SSR that Wire 229 was just removed from and to frame ground. The relay should energize closed. Set a voltmeter to measure resistance. Connect meter test leads across TEST POINTS A INFINITY should be measured. Connect meter test leads across TEST POINTS B continuity/ closed should be measured. Connect meter test leads across TEST POINTS C continuity/closed should be measured. See Figure 6.43. If the SSR fails any test replace it.

RESULTS:

Refer to Flow Chart.

1418

 

1

 

2

4

15B

15

5

 

6

8

 

 

 

 

 

 

9

 

10

12

 

15

 

13

 

14

0

 

SSR

 

TEST 32 - TEST START STOP RELAY (SSR)

PROCEDURE:

15

229

1.

Set a voltmeter to measure DC voltage.

2.

Remove Wire 15 from Terminal 13 on the Start Stop Relay

 

(SSR). Connect the positive meter test lead to Wire 15 previ-

 

ously removed. Connect the negative meter test lead to frame

 

ground. 12 VDC should be measured, if it is proceed to Step 3.

 

If 12 VDC is not measured repair or replace Wire 15 between

 

the SSR and the Battery Charge Rectifier 2 (BCR2).

3.

With Wire 15 reconnected to the SSR remove Wire 229 from

 

the SSR. Connect a jumper lead from the terminal of the SSR

 

that Wire 229 was just removed from and to frame ground. See

 

Figure 6-43. The relay should energize closed, visually inspect

 

it to see if it closes. If the relay energizes closed proceed to

 

Step 4. If the relay does not energize closed replace it.

4.

Remove Wire 0, Wire 18, Wire 15, Wire 15B, Wire 15, and Wire

Figure 6-41. – Start Stop Relay (SSR)

 

14

TEST POINTS C

 

18

 

 

TEST POINTS B

 

 

 

 

 

 

 

 

 

TEST POINTS A

 

 

 

1

 

2

4

15B

15

 

5

 

6

8

 

 

 

 

 

 

 

 

 

9

 

10

12

 

15

 

 

13

SSR 14

 

0

 

 

 

 

14. See Figure 6-42.

5. Set a voltmeter to measure resistance. Remove jumper lead

from Step 3. Connect meter test leads across TEST POINTS

15

229

A continuity/closed should be measured. Connect meter test

Figure 6-42. – Start Stop Relay (SSR) Not Energized

Page 54

Page 56
Image 56
Guardian Technologies 4582 & 4987, 4451 & 4986 Test 31 Remove Wire 18 / Shutdown Lead, Test 32 Test Start Stop Relay SSR