Section 3
DESCRIPTION & COMPONENTS
The resulting direct current from the BCR is delivered to the 12 VDC receptacle, via Wire 13A, CB1, and Wire 15A. This receptacle allows the capability to recharge a 12 volt DC storage battery with provided battery charge cables.
Insulation Resistance
The insulation resistance of stator and rotor wind- ings is a measurement of the integrity of the insulat- ing materials that separate the electrical windings from the generator steel core. This resistance can degrade over time or due to such contaminants as dust, dirt, oil, grease and especially moisture. In most cases, failures of stator and rotor windings is due to a breakdown in the insulation. In many cases, a low insulation resistance is caused by moisture that collects while the generator is shut down. When problems are caused by moisture buildup on the windings, they can usually be corrected by drying the windings. Cleaning and drying the windings can usu- ally eliminate dirt and moisture built up in the genera- tor windings.
The Megohmmeter
GENERAL:
A megohmmeter, often called a “megger”, consists of a meter calibrated in megohms and a power supply. Use a power supply of 500 volts when testing stators or rotors. DO NOT APPLY VOLTAGE LONGER THAN ONE (1) SECOND.
TESTING STATOR INSULATION:
All parts that might be damaged by the high meg- ger voltages must be disconnected before testing. Isolate all stator leads (Figure
Use a megger power setting of 500 volts. Connect one megger test lead to the junction of all stator leads, the other test lead to frame ground on the stator can. Read the number of megohms on the meter.
The MINIMUM acceptable megger reading for stators may be calculated using the following formula:
MINIMUM INSULATION |
| GENERATOR RATED VOLTS |
| |
RESISTANCE | = | __________________________ | +1 | |
1000 | ||||
(in “Megohms”) |
|
| ||
|
|
| ||
|
|
|
|
EXAMPLE: Generator is rated at 120 volts AC. Divide “120” by “1000” to obtain “0.12”. Then add “1” to obtain “1.12” megohms. Minimum insulation resistance for a 120 VAC stator is 1.12 megohms.
If the stator insulation resistance is less than the cal- culated minimum resistance, clean and dry the stator. Then, repeat the test. If resistance is still low, replace the stator.
Use the Megger to test for shorts between isolated
windings as outlined “Stator Insulation Tests”.
Also test between parallel windings. See “Test Between Windings” on next page.
TESTING ROTOR INSULATION:
Apply a voltage of 500 volts across the rotor positive
(+)slip ring (nearest the rotor bearing), and a clean frame ground (i.e. the rotor shaft). DO NOT EXCEED 500 VOLTS AND DO NOT APPLY VOLTAGE LONGER THAN 1 SECOND. FOLLOW THE MEGGER MANUFACTURER’S INSTRUCTIONS CAREFULLY.
ROTOR MINIMUM INSULATION RESISTANCE:
1.5megohms
* CAUTION: Before attempting to measure
Insulation resistance, first disconnect and Isolate all leads of the winding to be tested. Electronic components, diodes, surge protec- tors, relays, Voltage Regulators, etc., can be destroyed if subjected to high megger volt- ages.
HI-POT TESTER:
A
Figure 3-8. – One Type of Hi-Pot Tester
Stator Insulation Resistance Test
GENERAL:
Units with
Page 13