Section 6

DIAGNOSTIC TESTS

Loose cylinder head bolts.

Failed cylinder head gasket.

Burned valves or valve seats.

Insufficient valve clearance.

Warped cylinder head.

Warped valve stem.

Worn or broken piston ring(s).

Worn or damaged cylinder bore.

Broken connecting rod.

Worn valve seats or valves.

Worn valve guides.

NOTE: Refer to Engine Service manual No. 0F6923 for further engine service information.

Test 42 - Check Oil Pressure Switch

and Wire 86

If the engine cranks and starts, then shuts down almost immediately, the cause may be one or more of the following:

Low engine oil level.

Low oil pressure.

A defective oil pressure switch.

LOW OIL SWITCH

Figure 6-53. – Low Oil Pressure Switch

PROCEDURE:

1.Check engine crankcase oil level.

a.Check engine oil level.

b.If necessary, add the recommended oil to the dipstick FULL mark. DO NOT OVERFILL ABOVE THE FULL MARK.

2.Do the following:

a.Disconnect Wire 86 and Wire 0 from the oil pressure switch terminals. Remove the switch and install an oil pressure gauge in its place.

b. Start the engine while observing the oil pressure reading on gauge.

c. Note the oil pressure.

(1)Normal oil pressure is approximately 35-40 psi with engine running. If normal oil pres- sure is indicated, go to Step 4 of this test.

(2)If oil pressure is below about 10 psi, shut engine down immediately. A problem exists in the engine lubrication system. Refer to Service Manual, Generac P/N 0F6923 for engine service recommendations.

Note: The oil pressure switch is rated at 10 psi for v-twin engines.

3.Remove the oil pressure gauge and reinstall the oil pressure switch. Do NOT connect Wire 86 or Wire 0 to the switch termi- nals.

a.Set a voltmeter to measure resistance.

b.Connect the meter test leads across the switch terminals. With engine shut down, the meter should read CONTINUITY.

c.Crank and start the engine. The meter should read INFINITY.

d.Connect one test lead to Wire 0 ( disconnected from LOP). Connect the other test lead to a clean frame ground. Continuity should be measured. If con- tinuity is NOT measured repair or replace Wire 0 between the LOP and the ground terminal connection on the engine mount.

4.If the LOP switch tests good in Step 3 and oil pressure is good in Step 2, but the unit still shuts down with a LOP fault, check Wire 86 for a short to ground. Set a voltmeter to measure resistance. Disconnect the J2 Connector from the circuit board. Remove Wire 86 from the LOP switch. Connect one test lead to Wire 86. Connect the other test lead to a clean frame ground. INFINITY should be measured. If CONTINUITY is measured, repair or replace Wire 86 between the LOP switch and the J2 Connector.

RESULTS:

1.If switch tests good, refer to Flow Chart.

2.Replace switch if it fails the test.

TEST 43 - Check Start Stop Relay (SSR)

PROCEDURE:

1.Set a voltmeter to measure resistance.

2.Disconnect Wire 15 and Wire 229 from the Start Stop Relay (SSR). See Figure 6-54.

3.Connect one meter test lead to the terminal that Wire 15 was removed from. Connect the other meter test lead to the terminal that Wire 229 was removed from. Resistance measured should be approximately 100 ohms.

Page 60

Page 62
Image 62
Guardian Technologies 4583, 4582 & 4987, 5308 Test 42 Check Oil Pressure Switch Wire, Test 43 Check Start Stop Relay SSR

5308, 4583, 4451 & 4986, 4582 & 4987 specifications

Guardian Technologies has carved a niche in the market with its innovative air purification and UV-C sanitization products. The company's model numbers, including 4582, 4987, 4451, 4986, 4583, and 5308, represent a diverse range of solutions designed to enhance indoor air quality and safety in both residential and commercial settings.

The Guardian Technologies 4582 is equipped with a true HEPA filter that captures 99.97% of dust, pollen, smoke, and other particles as small as 0.3 microns. This model features a smart sensor that adjusts the fan speed according to the air quality in real-time. The UV-C light technology integrated into this device works to eliminate viruses and bacteria, providing an additional layer of protection against airborne pathogens.

The 4987 model follows suit with similar advanced features but adds a sleek design ideal for modern interiors. With multiple speed settings and a night mode, the 4987 is perfect for bedrooms or quiet spaces. Its energy-efficient operation coupled with an indicator that signals filter replacement ensures that users maintain optimal performance effortlessly.

The Guardian Technologies 4451 and 4986 models are particularly notable for their enhanced capacity and filtration efficiency. Both units incorporate a three-in-one filtration system that includes a pre-filter, activated charcoal filter, and HEPA filter. With their strategic design, these models not only purify the air but also trap common household odors, making them a popular choice for families with pets.

The 4583 model stands out with a unique combination of design and functionality. It features a low-profile design, making it easy to fit into any space. Its UV-C light technology not only disinfects air but can also sanitize surfaces, bridging the gap between air purification and direct sanitation.

Finally, the Guardian Technologies 5308 caters to larger spaces, offering impressive air circulation and filtration capabilities. Equipped with a high-efficiency particulate air (HEPA) filter and a powerful fan, it effectively cleans larger areas while maintaining whisper-quiet operation.

In summary, Guardian Technologies’ products exemplify a commitment to improving air quality and promoting health through innovative technology. With features like HEPA filtration, UV-C sanitization, smart sensors, and sleek designs, consumers can choose from a range of models that best fit their needs, ensuring cleaner, safer indoor environments.