Section 6
DIAGNOSTIC TESTS
00.00 | 20/30A |
C.B. |
TEST 4 - FIXED EXCITATION TEST/
ROTOR AMP DRAW
PROCEDURE:
*NOTE: If the generator is not producing AC Power, loss of governor control may occur caus- ing an overspeed or extremely high RPM condi- tion. If this condition occurs manually control throttle (60Hz /3600 RPM) to perform test.
1.Unplug the six pin connector at the Voltage Regulator.
2.Disconnect Wire 14 from the Resistor (R1).
Figure 6-8. – 20/30 Amp Breaker Test Points
TEST 3 - TEST EXCITATION CIRCUIT BREAKER
PROCEDURE:
1.With the generator shut down for at least two minutes, locate the Excitation Circuit Breaker in the control panel. Disconnect wires from the breaker, to prevent interaction.
2.Set a volt meter to measure resistance.
3.Connect the VOM test probes across the circuit breaker termi- nals. The meter should read CONTINUITY.
RESULTS:
1.If circuit breaker tests bad (meter reads “OPEN”) then proceed to Test 4 and replace the breaker after completing Test 4.
2.If circuit breaker is good, go on to Test 4.
00.00
162
2
Figure 6-9. - Testing Excitation Circuit Breaker
3.Connect a jumper wire between the removed end of Wire 14 and Wire 4 where it is soldered at the Diode (D1). See Figure
14 |
| |
| R1 | |
14 |
| |
| D2 | |
4 |
| |
4 |
| |
14 |
| |
WIRE 14 |
| |
REMOVED | R1 | |
14 | ||
| ||
JUMPER LEAD |
| |
| D2 | |
4 |
| |
4 |
|
Figure 6-10. – Jumper Lead From Wire 14 to Diode
4.Set voltmeter to measure AC voltage
5.Disconnect Wire 2 from the Excitation Circuit Breaker and con- nect one meter test lead to it. Connect the other meter test lead to Wire 6 located in the six pin connector previously removed from the Voltage Regulator. Be careful not to damage the pin connectors with the test leads. See Figure
6.Set Idle control switch to OFF.
7.Start the generator.
8.Measure the output voltage across Wire 2 and Wire 6 and record the results.
AC Voltage across Wires 2 and 6 = _____________
Page 38