Section 6
DIAGNOSTIC TESTS
TEST 11 - EXCITATION WIRING
PROCEDURE:
1.Set a voltmeter to measure resistance.
2.Disconnect Connector C1. See Page 17 for connector location.
3.Locate the male side of the connector located on the bottom of the control panel. See Figure
4.Unplug the six pin connector at the Voltage Regulator.
5.Locate the male side of the C1 connector located on the bot- tom of the control panel. Connect one meter test lead to Pin 7, Wire 6. It may be helpful to connect a small jumper lead to the individual pin. Connect the other meter Test lead to Wire 6 located in the six pin connector previously removed from the Voltage Regulator. Be careful not to damage the pin connectors with the test leads. Continuity should be measured.
RESULTS:
1.If continuity was not measured in any of the steps repair or replace wire.
2.If all steps pass refer back to flow chart.
TEST 12 - CHECK BRUSH LEADS
PROCEDURE:
1.Set a voltmeter to measure resistance.
2.Disconnect Connector C1. See Page 17 for connector location.
3.See Figure
4.Remove the control panel assembly to access the brushes. See Figure
5.Connect one meter test lead across Wire 0 (Pin 12) at the C1 connector female side. Be careful not to damage the pin connectors with the test leads, use paper clips - do not force probes into connectors. Connect the other meter test lead to Wire 0 at the brush assembly. Continuity should be measured. If INFINITY is measured repair or replace Wire 0.
6.Unplug the six pin connector at the Voltage Regulator.
7.Locate the male side of Connector C1 located on the bottom of the control panel. See Figure
8.Connect one meter test lead to Pin 12 Wire 0. See Figure
RESULTS:
1.Repair or replace wiring/terminals as needed.
2.If no faults are found refer to flow chart.
4 0
Figure 6-20. – Brush Leads
Test 13 - Check Brushes & Slip Rings
PROCEDURE:
1. Gain access to the brushes and slip rings.
Page 45