Section 6

DIAGNOSTIC TESTS

TEST 11 - EXCITATION WIRING

PROCEDURE:

1.Set a voltmeter to measure resistance.

2.Disconnect Connector C1. See Page 17 for connector location.

3.Locate the male side of the connector located on the bottom of the control panel. See Figure 6-19. Connect one meter test lead to Pin 6 Wire 2, it may be helpful to connect a small jumper lead to the individual pin. Disconnect Wire 2 from the Excitation Circuit Breaker (CB1). Connect the other meter test lead to Wire 2 . See Page 17 for Excitation Circuit Breaker loca- tion. Continuity should be measured.

4.Unplug the six pin connector at the Voltage Regulator.

5.Locate the male side of the C1 connector located on the bot- tom of the control panel. Connect one meter test lead to Pin 7, Wire 6. It may be helpful to connect a small jumper lead to the individual pin. Connect the other meter Test lead to Wire 6 located in the six pin connector previously removed from the Voltage Regulator. Be careful not to damage the pin connectors with the test leads. Continuity should be measured.

RESULTS:

1.If continuity was not measured in any of the steps repair or replace wire.

2.If all steps pass refer back to flow chart.

TEST 12 - CHECK BRUSH LEADS

PROCEDURE:

1.Set a voltmeter to measure resistance.

2.Disconnect Connector C1. See Page 17 for connector location.

3.See Figure 6-18. Connect the meter test leads across Wire 4 (Pin 11) and Wire 0 (Pin 12) at the C1 connector female side. Be careful not to damage the pin connectors with the test leads, use paper clips - do not force probes into connectors. Rotor resistance should be measured approximately 7-14 ohms. If resistance is measured proceed to Step 6. If no resis- tance is measured continue.

4.Remove the control panel assembly to access the brushes. See Figure 6-21. Connect one meter test lead across Wire 4 (Pin 11) at the C1 connector female side. Be careful not to damage the pin connectors with the test leads, use paper clips - do not force probes into connectors. Connect the other meter test lead to Wire 4 at the brush assembly. Continuity should be measured. If INFINITY is measured repair or replace Wire 4.

5.Connect one meter test lead across Wire 0 (Pin 12) at the C1 connector female side. Be careful not to damage the pin connectors with the test leads, use paper clips - do not force probes into connectors. Connect the other meter test lead to Wire 0 at the brush assembly. Continuity should be measured. If INFINITY is measured repair or replace Wire 0.

6.Unplug the six pin connector at the Voltage Regulator.

7.Locate the male side of Connector C1 located on the bottom of the control panel. See Figure 6-19. Connect one meter test lead to Pin 11 Wire 4. Connect the other meter test lead to Wire 4 at the six pin connector previously removed from the Voltage Regulator. See Figure 6-11. Be careful not to damage the pin connectors with the test leads. Continuity should be measured. If continuity is not measured repair or replace Wire 4 between the C1 connector and the six-pin Voltage Regulator connector.

8.Connect one meter test lead to Pin 12 Wire 0. See Figure 6-19. Connect the other meter test lead to the ground terminal in the control panel. Continuity should be measured. If continuity is not measured repair or replace Wire 0 between the C1 connec- tor and the ground terminal.

RESULTS:

1.Repair or replace wiring/terminals as needed.

2.If no faults are found refer to flow chart.

4 0

Figure 6-20. – Brush Leads

Test 13 - Check Brushes & Slip Rings

PROCEDURE:

1. Gain access to the brushes and slip rings.

Page 45

Page 47
Image 47
Guardian Technologies 5308, 4583 Test 11 Excitation Wiring, Test 12 Check Brush Leads, Test 13 Check Brushes & Slip Rings

5308, 4583, 4451 & 4986, 4582 & 4987 specifications

Guardian Technologies has carved a niche in the market with its innovative air purification and UV-C sanitization products. The company's model numbers, including 4582, 4987, 4451, 4986, 4583, and 5308, represent a diverse range of solutions designed to enhance indoor air quality and safety in both residential and commercial settings.

The Guardian Technologies 4582 is equipped with a true HEPA filter that captures 99.97% of dust, pollen, smoke, and other particles as small as 0.3 microns. This model features a smart sensor that adjusts the fan speed according to the air quality in real-time. The UV-C light technology integrated into this device works to eliminate viruses and bacteria, providing an additional layer of protection against airborne pathogens.

The 4987 model follows suit with similar advanced features but adds a sleek design ideal for modern interiors. With multiple speed settings and a night mode, the 4987 is perfect for bedrooms or quiet spaces. Its energy-efficient operation coupled with an indicator that signals filter replacement ensures that users maintain optimal performance effortlessly.

The Guardian Technologies 4451 and 4986 models are particularly notable for their enhanced capacity and filtration efficiency. Both units incorporate a three-in-one filtration system that includes a pre-filter, activated charcoal filter, and HEPA filter. With their strategic design, these models not only purify the air but also trap common household odors, making them a popular choice for families with pets.

The 4583 model stands out with a unique combination of design and functionality. It features a low-profile design, making it easy to fit into any space. Its UV-C light technology not only disinfects air but can also sanitize surfaces, bridging the gap between air purification and direct sanitation.

Finally, the Guardian Technologies 5308 caters to larger spaces, offering impressive air circulation and filtration capabilities. Equipped with a high-efficiency particulate air (HEPA) filter and a powerful fan, it effectively cleans larger areas while maintaining whisper-quiet operation.

In summary, Guardian Technologies’ products exemplify a commitment to improving air quality and promoting health through innovative technology. With features like HEPA filtration, UV-C sanitization, smart sensors, and sleek designs, consumers can choose from a range of models that best fit their needs, ensuring cleaner, safer indoor environments.