Section 6

DIAGNOSTIC TESTS

measure at the battery terminals during cranking. If battery voltage is below 11 volts DC, recharge/replace battery. If bat- tery or cables are still suspected, connect an alternate battery and cables to the generator and retest.

2.Use a battery hydrometer to test the battery for (a) state of charge and (b) condition. Follow the hydrometer manufacturer's instructions carefully.

RESULTS:

1.Clean battery posts and cables as necessary. Make sure bat- tery cables are tight.

2.Recharge the battery, if necessary.

3.Replace the battery, if necessary.

4.If battery is good, but engine will not crank, refer back to Flow Charts.

TEST 23 - Check Voltage at Starter

Contactor (SC)

PROCEDURE:

1.Set voltmeter to measure DC voltage.

2.Disconnect Wire 16 from the Starter Contactor located on the Starter motor.

3.Connect the positive meter test lead to Wire 16 previous- ly removed. Connect the negative meter test lead to frame Ground.

4.Place the Start-Run-Stop Switch to Start. 12 VDC should be measured.

5.Reconnect Wire 16 to the Starter Motor.

RESULTS:

Refer back to flow chart.

Test 24 - Check Starter Contactor (SC)

PROCEDURE:

1.Carefully inspect the starter motor cable that runs from the Battery to the Starter Motor. Cable connections should be clean and tight. If connections are dirty or corroded, remove cable and clean cable terminals and studs. Replace any cable that is defective or badly corroded. Set the voltmeter to mea- sure DC voltage. Connect the positive (+) meter test lead to the Starter Contactor stud that the battery cable is connected to. Connect the negative (-) meter test lead to a clean frame ground. Battery voltage should be measured (see Figure 6-28,

STEP 1 TEST POINT).

 

STARTER

16

 

 

 

SWITCH

50

 

 

BATTERY

30

 

12V

 

 

CONNECTING

DIAGRAM

 

PERMANENT MAGNET

STARTER

step 1

TEST POINT

CONTACTOR

 

 

step 2

 

TEST POINT

STARTER

 

MOTOR

 

Figure 6-28. – The Starter Contactor (SC)

2.Set the voltmeter to measure DC voltage. Connect the positive

(+)meter test lead to the Starter Contactor stud that has the small jumper wire connected to the Starter. Connect the nega- tive (-) meter test lead to a clean frame ground. Set the Start- Stop Switch to Start. Battery voltage should be measured (see Figure 6-28, STEP 2 TEST POINT).

RESULTS:

1. If battery voltage was not measured in Step 1, repeat Test 22.

2If battery voltage was measured in Step 1, but not in Step 2, replace the Starter Contactor.

4.If battery voltage was measured in Step 2 but the engine still does not crank, refer back to the Flow Chart.

Test 25 - Check Starter Motor

Conditions Affecting Starter Motor Performance:

1.A binding or seizing condition in the Starter Motor bearings.

2.A shorted, open or grounded armature.

a.Shorted, armature (wire insulation worn and wires touching one another). Will be indicated by low or no RPM.

b.Open armature (wire broken) will be indicated by low or no RPM and excessive current draw.

c.Grounded armature (wire insulation worn and wire touching armature lamination or shaft). Will be indicated by excessive current draw or no RPM.

Page 49

Page 51
Image 51
Guardian Technologies 5308, 4582 & 4987 Test 23 Check Voltage at Starter Contactor SC, Test 24 Check Starter Contactor SC

5308, 4583, 4451 & 4986, 4582 & 4987 specifications

Guardian Technologies has carved a niche in the market with its innovative air purification and UV-C sanitization products. The company's model numbers, including 4582, 4987, 4451, 4986, 4583, and 5308, represent a diverse range of solutions designed to enhance indoor air quality and safety in both residential and commercial settings.

The Guardian Technologies 4582 is equipped with a true HEPA filter that captures 99.97% of dust, pollen, smoke, and other particles as small as 0.3 microns. This model features a smart sensor that adjusts the fan speed according to the air quality in real-time. The UV-C light technology integrated into this device works to eliminate viruses and bacteria, providing an additional layer of protection against airborne pathogens.

The 4987 model follows suit with similar advanced features but adds a sleek design ideal for modern interiors. With multiple speed settings and a night mode, the 4987 is perfect for bedrooms or quiet spaces. Its energy-efficient operation coupled with an indicator that signals filter replacement ensures that users maintain optimal performance effortlessly.

The Guardian Technologies 4451 and 4986 models are particularly notable for their enhanced capacity and filtration efficiency. Both units incorporate a three-in-one filtration system that includes a pre-filter, activated charcoal filter, and HEPA filter. With their strategic design, these models not only purify the air but also trap common household odors, making them a popular choice for families with pets.

The 4583 model stands out with a unique combination of design and functionality. It features a low-profile design, making it easy to fit into any space. Its UV-C light technology not only disinfects air but can also sanitize surfaces, bridging the gap between air purification and direct sanitation.

Finally, the Guardian Technologies 5308 caters to larger spaces, offering impressive air circulation and filtration capabilities. Equipped with a high-efficiency particulate air (HEPA) filter and a powerful fan, it effectively cleans larger areas while maintaining whisper-quiet operation.

In summary, Guardian Technologies’ products exemplify a commitment to improving air quality and promoting health through innovative technology. With features like HEPA filtration, UV-C sanitization, smart sensors, and sleek designs, consumers can choose from a range of models that best fit their needs, ensuring cleaner, safer indoor environments.