Section 6

DIAGNOSTIC TESTS

Connect one meter test lead to pin location J2-10 Wire 44S of the connector just removed. Be careful not to damage the pin connectors with the test leads. Connect the other meter test lead to Wire 44S at Terminal Block 2 (TB2). CONTINUITY should be measured.

3.Connect one meter test lead to pin location J2-12 Wire 11S. Be careful not to damage the pin connectors with the test leads. Connect the other meter test lead to Wire 11S at Terminal Block 2 (TB2). CONTINUITY should be measured.

 

44S 11S

 

 

 

00.00

 

TB2

 

 

STEP 2

 

 

STEP 3

 

 

STEP 2

STEP 3

J2-1

J2-12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAKE SURE THE TEST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROBE CONNECTOR IS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAKING CONTACT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WITH THE CONNECTOR.

J2 HARNESS CONNECTOR

DOUBLE CHECK TO

MAKE SURE THAT THE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TIP IS SHARP.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 6-58. – Check Wires 11S & 44S

RESULTS:

1.If CONTINUITY was not measured, repair or replace the wire harness.

2.If CONTINUITY was measured, refer back to the flow chart.

TEST 52 - CHECK IDLE CONTROL SWITCH

(SW2)

PROCEDURE:

1.Set a voltmeter to measure resistance.

2.Disconnect Wire 0 and Wire 83 from the Idle Control Switch (SW2).

3.Connect meter test leads across both terminals of SW2. See Figure 6-59.

4.In the OFF position the meter should read INFINITY or Open. In the ON position the meter should read CONTINUITY or Closed.

RESULTS:

1.If the switch fails Step 4 replace it.

2.If the switch is good refer back to the flow chart.

SW2

OFFON

OL

00.00

Figure 6-59. – Check Idle Control Switch (SW2)

TEST 53 - CHECK IDLE CONTROL WIRING

PROCEDURE:

1.Set a voltmeter to measure resistance.

2.Disconnect Wire 0 from the Idle Control Switch (SW2).

3.Connect one meter test lead to Wire 0. Connect the other meter test lead to frame ground. CONTINUITY should be measured. If continuity is not measured repair or replace Wire 0 between SW2 and the ground terminal.

4.Disconnect Wire 83 from SW2. Disconnect the J2 connector from the printed circuit board.

5.Connect one meter test lead to Wire 83 previously removed from SW2. Connect the other meter test lead to pin location J2-2 on the J2 connector. See Figure 6-60. Be careful not to damage the pin connectors with the test leads. CONTINUITY should be measured. If CONTINUITY is not measured repair or replace Wire 83 between the J2 connector and Terminal Block or between the Terminal Block and SW2.

Page 63

Page 65
Image 65
Guardian Technologies 4451 & 4986, 4583 Test 52 Check Idle Control Switch, SW2, Test 53 Check Idle Control Wiring, TB2

5308, 4583, 4451 & 4986, 4582 & 4987 specifications

Guardian Technologies has carved a niche in the market with its innovative air purification and UV-C sanitization products. The company's model numbers, including 4582, 4987, 4451, 4986, 4583, and 5308, represent a diverse range of solutions designed to enhance indoor air quality and safety in both residential and commercial settings.

The Guardian Technologies 4582 is equipped with a true HEPA filter that captures 99.97% of dust, pollen, smoke, and other particles as small as 0.3 microns. This model features a smart sensor that adjusts the fan speed according to the air quality in real-time. The UV-C light technology integrated into this device works to eliminate viruses and bacteria, providing an additional layer of protection against airborne pathogens.

The 4987 model follows suit with similar advanced features but adds a sleek design ideal for modern interiors. With multiple speed settings and a night mode, the 4987 is perfect for bedrooms or quiet spaces. Its energy-efficient operation coupled with an indicator that signals filter replacement ensures that users maintain optimal performance effortlessly.

The Guardian Technologies 4451 and 4986 models are particularly notable for their enhanced capacity and filtration efficiency. Both units incorporate a three-in-one filtration system that includes a pre-filter, activated charcoal filter, and HEPA filter. With their strategic design, these models not only purify the air but also trap common household odors, making them a popular choice for families with pets.

The 4583 model stands out with a unique combination of design and functionality. It features a low-profile design, making it easy to fit into any space. Its UV-C light technology not only disinfects air but can also sanitize surfaces, bridging the gap between air purification and direct sanitation.

Finally, the Guardian Technologies 5308 caters to larger spaces, offering impressive air circulation and filtration capabilities. Equipped with a high-efficiency particulate air (HEPA) filter and a powerful fan, it effectively cleans larger areas while maintaining whisper-quiet operation.

In summary, Guardian Technologies’ products exemplify a commitment to improving air quality and promoting health through innovative technology. With features like HEPA filtration, UV-C sanitization, smart sensors, and sleek designs, consumers can choose from a range of models that best fit their needs, ensuring cleaner, safer indoor environments.