Parameter Locations, Descriptions, and Default Values

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

Address 1

Power plant address or identification -

Address 1

m+

Security Level {1}

first line.

APC DCNS, Inc.

 

[SYSTEM/SETUP]

 

 

 

Address 2

Power plant address or identification -

Address 2

m+

Security Level {1}

second line.

11035 Switzer Av

[SYSTEM/SETUP]

 

 

 

Address 3

Power plant address or identification -

Address 3

m+

Security Level {1}

third line.

Dallas, TX.

 

[SYSTEM/SETUP]

 

 

 

Alarms Item 1

Display of up to 16 active alarms (a

Alarm Item 1

+

{Status Only}

typical alarm screen is shown).

Batt LV Alm Onm

[ALARMS]

 

 

 

 

 

Display of up to 16 active alarms (a

 

Alarms Item 16

typical alarm screen is shown).

Alarm Item 16

+

[ALARMS]

 

No Alarms

 

Battery Current

Battery current measured by the system

Batt Current

+

{Status Only}

controller at the battery current shunt.

-15.0 A

[STATUS]

 

 

 

Battery Discharge Alarm

The output relay energized if the battery

Batt Disc Alm m+

Security Level {1}

discharge current exceeds the

Minor

 

[BATT/SET-ALM]

programmed battery discharge threshold.

 

 

Battery Discharge Threshold

An alarm is generated if the battery

Batt Disc Thr m+

Security Level {1}

discharge current exceeds this value.

10 A

[BATT/SET-ALM]

 

 

 

Battery Float Voltage

One of three parameters that control the

Batt Float

m+

Security Level {1}

output voltage. Set the Float Voltage at

27.00 V

[BATT/PARAM]

25°C battery temperature per the battery

 

 

 

manufacturers recommendations.

 

 

Battery High Temperature

The output relay energized if the battery

Batt HT Alm

m+

Alarm

temperature exceeds the Battery High

Minor

 

Security Level {1}

Temperature threshold.

 

 

[BATT/SET-ALM]

 

 

 

Battery High Temperature

Battery Temperature is temperature

Batt HT Thr

m+

Threshold

measured at the battery probe. An alarm

70.0 C

Security Level {1}

is generated if the battery temperature

 

 

[BATT/SET-ALM]

exceeds this value.

 

 

Battery High Voltage Alarm

The output relay energized if the dc

Batt HV Alm

m+

Security Level {1}

output voltage rises above the battery

Minor

 

[BATT/SET-ALM]

high voltage threshold.

 

 

Battery High Voltage Threshold

An alarm will be reported if temperature

Batt HV Thr

m+

Security Level {1}

is lower than the temperature entered.

28.00 V

[BATT/SET-ALM]

An alarm is generated if the dc output

 

 

 

voltage rises above this value.

 

 