Parameter Locations, Descriptions, and Default Values
PARAMETER NAME/ | DESCRIPTION | DISPLAY SCREENS / | |
[MENU LOCATION] |
| DEFAULT SETTINGS | |
|
|
| |
Rectifier Standby Alarm | The output relay that is energized or | Rect Stdby Almm+ | |
Security Level {1} | special rectifier alarm group n of N that | n of N |
|
| occurs when the control unit is holding a |
|
|
| rectifier in the standby mode. |
|
|
Rectifier Standby Alarm Status | The status will be “ON” if the control unit | Rect 1 Stdby | # |
{Status Only} | is holding the rectifier in the standby | OFF |
|
[MODULES/RECT/INFO] | mode. NOTE: This information can be |
|
|
| viewed for each rectifier installed by |
|
|
| using the horizontal arrow keys. |
|
|
Store Configuration | Setting this parameter to “Enable” will | Store Cfg | m+ |
Security Level {1} | cause the current rectifier configuration | Disable |
|
[SYSTEM/DIAG] | to be stored (the display toggles back to |
|
|
| “Disable” after entry). |
|
|
System Current | The total system output current | Sys Current | + |
{Status Only} | (calculated as the sum of the individual | 145.8 | A |
[STATUS] | rectifier output currents). |
|
|
System High Temperature | The output relay energized if the System | Sys HT Alm | m+ |
Alarm | Temperature exceeds the system high | Minor |
|
Security Level {1} | temperature threshold. |
|
|
|
|
| |
System High Temperature | System Temperature is ambient | Sys HT Thr | m+ |
Threshold | temperature measured inside the | 70.0 | C |
Security Level {1} | controller. An alarm will be reported if |
|
|
temperature is higher than the |
|
| |
| temperature entered. |
|
|
System High Voltage alarm | The output relay energized if the System | Sys HV Alm | m+ |
Security Level {1} | Voltage is above the System High | Minor |
|
Voltage threshold. |
|
| |
System High Voltage | System Voltage is bus voltage measured | Sys HV Thr | m+ |
Threshold | by the controller. An alarm will be | 29.00 | V |
Security Level {1} | reported if voltage is higher than the |
|
|
voltage entered. |
|
| |
System Low Temperature | The output relay energized if the System | Sys LT Alm | m+ |
Alarm | Temperature is below the System Low | Minor |
|
Security Level {1} | Temperature threshold. |
|
|
|
|
| |
System Low Temperature | System Temperature is ambient | Sys LT Thr | m+ |
Threshold | temperature measured inside the | 0.0 | C |
Security Level {1} | controller. An alarm will be reported if |
|
|
temperature is lower than the |
|
| |
| temperature entered. |
|
|
System Low Voltage Alarm | The output relay energized if the System | Sys LV Alm | m+ |
Security Level {1} | Voltage is below the System Low Voltage | Minor |
|
threshold. |
|
| |
System Low Voltage Threshold | System Voltage is bus voltage measured | Sys LV Thr | m+ |
Security Level {1} | by the controller. An alarm will be | 25.00 | V |
reported if voltage is lower than the |
|
| |
| voltage entered. |
|
|
MX28B400 +24 VDC User’s Manual | Page 32 |