Parameter Locations, Descriptions, and Default Values

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

Rectifier Current Limit Alarm

The output relay that is energized or

Rect CL Alm

m+

Security Level {1}

special rectifier alarm group n of N that

n of N

 

[MODULES/RECT/SET-ALM]

occurs when a rectifier has been forced

 

 

 

into the current limited mode.

 

 

Rectifier Current Limit Alarm

The status will be “ON” if the rectifier has

Rect 1 CL

#

Status

been forced into its current limited mode.

OFF

 

{Status Only}

NOTE: This information can be

 

 

[MODULES/RECT/INFO]

viewed for each rectifier installed by

 

 

 

using the horizontal arrow keys.

 

 

Rectifier Current Output Status

A display of the dc output current for the

Rect 1 Curr

#

{Status Only}

individual rectifier. NOTE: This

24.9

A

[MODULES/RECT/INFO]

information can be viewed for each

 

 

 

rectifier installed by using the

 

 

 

horizontal arrow keys.

 

 

Rectifier Description

Displays the model number of the

Rect 1 Desc

#

{Status Only}

installed rectifier. NOTE: This

MRF28H27

 

[MODULES/RECT/INFO]

information can be viewed for each

 

 

 

rectifier installed by using the

 

 

 

horizontal arrow keys.

 

 

Rectifier Fail 1-of-N Alarm

The output relay energized if Rectifier

Rect 1ofN Almm+

Security Level {1}

Fail 1-of-N alarm occurs. This is a

Minor

 

[SYSTEM/SET-ALM]

special rectifier alarm group that signifies

 

 

 

that one rectifier has at least one alarm

 

 

 

condition.

 

 

Rectifier Fail 2-of-N Alarm

The output relay energized if Rectifier

Rect 2ofN Almm+

Security Level {1}

Fail 2-of-N alarm occurs This is a special

Major

 

[SYSTEM/SET-ALM]

rectifier alarm group that signifies that

 

 

 

more than one rectifier has at least one

 

 

 

alarm condition.

 

 

Rectifier Fail Safe Voltage

Rectifier default output voltage if

Rect Fail Safem+

Security Level {1}

communication with the control unit fails.

+27.00 V

[MODULES/RECT/PARAM]

 

 

 

Rectifier Fan Fail Alarm

The output relay that is energized or

Rect FF Alm

m+

Security Level {1}

special rectifier alarm group n of N that

n of N

 

[MODULES/RECT/SET-ALM]

occurs when a rectifier fan has failed.

 

 

Rectifier Fan Fail Alarm Status

The status will be “ON” if the rectifier fan

Rect 1 FF

#

{Status Only}

has failed. NOTE: This information

OFF

 

[MODULES/RECT/INFO]

can be viewed for each rectifier

 

 

 

installed by using the horizontal arrow

 

 

 

keys.

 

 

Rectifier Fault Alarm (RFA)

The status will be on if the rectifier output

Rect 1 RFA

#

Status

has failed. NOTE: This information

OFF

 

{Status Only}

can be viewed for each rectifier

 

 

[MODULES/RECT/INFO]

installed by using the horizontal arrow

 

 

 

keys.

 

 

Rectifier RFA Alarm

The output relay that is energized or

Rect RFA Alm

m+

Security Level {1}

special rectifier alarm group n of N that

n of N

 

[MODULES/RECT/SET-ALM]

occurs when a rectifier output has failed.

 

 

MX28B400 +24 VDC User’s Manual

Page 31

Page 35
Image 35
American Power Conversion MX28B400 Rect CL Alm, Rect 1 CL, Rect 1 Curr, 24.9, Rect 1 Desc, MRF28H27, Rect 1ofN Almm+