Installation

Using AXlink for data with an auxiliary power supply

Connect the Controller’s AXlink connector to the AXlink connector on the rear panel of the AXR- NWS, as shown in FIG. 6.

PWR (+)

AXP

AXM GND (-)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PWR (+)

12 VDC power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND (-)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PWR (+)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AXP

Controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AXM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND (-)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AXR-NWS (3.5 mm connector)

FIG. 6 AXlink and 12 VDC power supply wiring diagram

If you are not using power from AXlink, disconnect the wiring from the Controller before wiring the AXR-NWS. Make sure the auxiliary power supply’s PWR (+) is not connected to the Central Controller’s AXlink connector.

Use an auxiliary 12 VDC power supply when the distance between the Central Controller and Server exceeds the limits described in Wiring Guidelines table. Connect only the GND (-) wire on the AXlink connector when using an auxiliary 12 VDC power supply.

Preparing captive wires

1.Strip 0.25" of wire insulation off the ends of all wires.

2.Insert each wire end into the appropriate opening on the connector according to the wiring diagrams and connector types described in theUsing AXlink for data and power section on page 7. Do not tighten the screws excessively; doing so may strip threads and damage the connector.

Installing the Control System

1.Install the AXR-NWS on any flat surface.

2.Rotate the RF antenna to a vertical position to communicate with the touch panels.

3.Verify that the Server DIP switch settings are configured with the correct GROUP ADDRESS and GROUP ID.

4.Verify the touch panels have the same GROUP ID value as the Server.

5.Connect the Server to the Central Controller (FIG. 7) by connecting the 3.5 mm 4-pin AXlink cable from the bus connector to the AXlink connector at the rear of the Central Controller.

 

8

AXR-NWS NetWave Server

 

 

 

Page 12
Image 12
AMX AXR-NWS Installing the Control System, Using AXlink for data with an auxiliary power supply, Preparing captive wires