Mechanical inspection checklist
The mechanical inspection verifies that all mechanical components and connections are secure and tight and ready for
Warning: The equipment is shipped from the factory with a nitrogen holding charge. Remove the nitrogen holding charge using the Schrader valves located on the internal refrigerant piping.
Caution: Improperly installed piping may result in improper operation and possible damage to the cooling unit or surrounding equipment.
Ensure that the:
Fans are turning freely and that the blades are not distorted or bent.
Condensate drain line is at least the size of the drain connection.
Piping joints are tight.
Mechanical connections are tight, including compressor and receiver rotolock connections.
Refrigerant piping size is correct according to the line size table in the installation manual.
Vertical, horizontal, and total run lengths of the liquid, discharge, and suction lines are recorded.
Number of 45- and
Refrigerant piping is adequately supported and isolated when necessary.
Pressure relief valve is installed in accordance with the installation manual as well as local and national codes and regulations.
Piping in the building and on the roof is properly insulated.
Covers and guards are in place.
InRow RD 10 kW Air Cooled Operation and Maintenance | 5 |