USER’S GUIDE
network management card
46
Control Console. From Device Manager, type 1 to select DC Power

Plant, then type 1 again to select DC System. The following options are

displayed.

1- DC System Parameters

2- OEM Parameters

From the DC System menu, type 1 to select DC System Parameters,

which displays the following menu items:

Menu Item Description
1- Description1 Descriptions related to your DC Power Plant system.
Maximum per field: 16 characters.
2- Description2
3- Description3
4- High
Temperature
The ambient high temperature threshold.
Minimum: 0 ° Celsius
Maximum: 100.00° Celsius
5- High
Temperature
Alarm
The alarm action to occur when the ambient high temperature
threshold (item 4 above) is violated.
Allowed values: any standard alarm selection.a
6- Low
Temperature
The ambient low temperature threshold.
Minimum: – 100.00° Celsius
Maximum: 100.00° Celsius
7- Low
Temperature
Alarm
The alarm action to occur when the ambient low temperature
threshold (item 6 above) is violated.
Allowed values: any standard alarm selection.a
a Standard alarm selections
Major activates the major relay.
Minor activates the minor relay.
Relay 1 through Relay 6 activates the relay specified.
Ignore ignores the alarm.