Programming parameters

*Text in bold letters are the factory standard setting

**Advanced Battery Monitor

***Viewable only in a parallel configuration.

NOTE:

Common battery pack is a technical possibility. However, APC recommend separate battery pack due to a higher safety degree in con- nection with redundant/parallel operation.

The UPS system is prepared for both solutions.

7OA0004 US rev. 02

4.3Programming of system configuration parameters

The system configuration parameters are protected by a password because most of them are critical for correct operation of the system.

Wrong programming can for example destroy the battery or cause loss of output voltage during operation!!

4.3.1 System configuration parameters

Parameter

Setting*

Comments

Isolation trafo utility

YES, NO

YES if optional input isolation transformer is

 

 

present

Isolation trafo output

YES, NO

YES if optional output isolation transformer is

 

 

present

Delta soft start time

1, 10, 20,

Input current switching in ramp function.

 

40 secs.

Higher values used together with smaller/

 

 

unstable diesel generators

External SSW present

YES, NO

YES for systems with external static bypass

 

 

switch

Normal charge voltage

438

Setting of float charge voltage at 20°C /68°F

 

 

(Aut. compensation for deviations)

 

 

 

Boost charge voltage

438

Setting of boost charge voltage at 20°C /68°F

 

 

(Aut. compensation for deviations)

 

 

 

Low battery warning

346

Warning for discharged battery

Low battery shut down

326

Switches off the system at min. permissible

 

 

battery voltage

 

 

 

Synchronization

0.25, 0.5, 1

Synchronisation speed. Higher values used

 

2, 4 Hz/sec

with very unstable utility frequencies

 

 

 

High battery temperature

15-40°C

Alarm for too high battery ambient

 

/59-104°F

temperature

 

35°C/95°F

 

 

 

 

Common fault delay

0, 10, 20

Delay before the common fault alarm relay is

 

30 secs.

activated

 

 

 

Reset operation mode

YES, NO

YES resets system locked in bypass or battery

lock

 

operation mode caused by system failures

 

 

(Only for service personnel)

 

 

 

Highest station address

2-9***

Highest station address in parallel system

Station address

1-9***

Station address in parallel system

 

 

 

Advanced power

None***

Only used in parallel system.

management (APM)

 

Off: Advanced power management disabled.

 

 

Parallel +1: Redundant operation with all units

 

 

in operation.

 

 

Redundant +1: Redundant operation with

 

 

one unit being inactive in parallel system

APM test mode active

YES, NO***

YES, if APM test mode is active (service

 

 

personnel only)

 

 

 

Battery connection

Common,

Common if common battery is used in parallel

 

Separate

system. Separate if separate battery is used

 

 

 

Expected back-up

0,1-999,9

Expected back-up time for UPS in minutes,

time [min.]

5,0

when running at 100% ohmic load.

 

 

Time used by the ABM**

 

 

 

Battery capacity

0,1-999,9

Total battery capacity in Ah.

in [Ah]

7,0

Setting used by the ABM**

 

 

 

18

User Guide Silcon DP300E Series 480V 400-500kVA

Page 18
Image 18
APC DP300E Series manual Programming of system configuration parameters, 438, 346, 326, 35C/95F