Programming parameters
*Text in bold letters are the factory standard setting
**Advanced Battery Monitor
***Viewable only in a parallel configuration.
NOTE:
Common battery pack is a technical possibility. However, APC recommend separate battery pack due to a higher safety degree in con- nection with redundant/parallel operation.
The UPS system is prepared for both solutions.
7OA0004 US rev. 02
4.3Programming of system configuration parameters
The system configuration parameters are protected by a password because most of them are critical for correct operation of the system.
Wrong programming can for example destroy the battery or cause loss of output voltage during operation!!
4.3.1 System configuration parameters
Parameter | Setting* | Comments |
Isolation trafo utility | YES, NO | YES if optional input isolation transformer is |
|
| present |
Isolation trafo output | YES, NO | YES if optional output isolation transformer is |
|
| present |
Delta soft start time | 1, 10, 20, | Input current switching in ramp function. |
| 40 secs. | Higher values used together with smaller/ |
|
| unstable diesel generators |
External SSW present | YES, NO | YES for systems with external static bypass |
|
| switch |
Normal charge voltage | 438 | Setting of float charge voltage at 20°C /68°F |
|
| (Aut. compensation for deviations) |
|
|
|
Boost charge voltage | 438 | Setting of boost charge voltage at 20°C /68°F |
|
| (Aut. compensation for deviations) |
|
|
|
Low battery warning | 346 | Warning for discharged battery |
Low battery shut down | 326 | Switches off the system at min. permissible |
|
| battery voltage |
|
|
|
Synchronization | 0.25, 0.5, 1 | Synchronisation speed. Higher values used |
| 2, 4 Hz/sec | with very unstable utility frequencies |
|
|
|
High battery temperature | Alarm for too high battery ambient | |
| temperature | |
| 35°C/95°F |
|
|
|
|
Common fault delay | 0, 10, 20 | Delay before the common fault alarm relay is |
| 30 secs. | activated |
|
|
|
Reset operation mode | YES, NO | YES resets system locked in bypass or battery |
lock |
| operation mode caused by system failures |
|
| (Only for service personnel) |
|
|
|
Highest station address | Highest station address in parallel system | |
Station address | Station address in parallel system | |
|
|
|
Advanced power | None*** | Only used in parallel system. |
management (APM) |
| Off: Advanced power management disabled. |
|
| Parallel +1: Redundant operation with all units |
|
| in operation. |
|
| Redundant +1: Redundant operation with |
|
| one unit being inactive in parallel system |
APM test mode active | YES, NO*** | YES, if APM test mode is active (service |
|
| personnel only) |
|
|
|
Battery connection | Common, | Common if common battery is used in parallel |
| Separate | system. Separate if separate battery is used |
|
|
|
Expected | Expected | |
time [min.] | 5,0 | when running at 100% ohmic load. |
|
| Time used by the ABM** |
|
|
|
Battery capacity | Total battery capacity in Ah. | |
in [Ah] | 7,0 | Setting used by the ABM** |
|
|
|
18 | User Guide Silcon DP300E Series 480V |