Programming Parameters

NOTE:

Only for APC personnel and certified local APC personnel.

4.4Programming of battery monitor

Action

 

 

Display shows

1. Press

and

simultaneously to open

Key in password

 

 

for password input

:

 

 

 

2.Enter password xx xx xx by pressing

Last selected

parameter

3. Press

or

until

Expected back-up

time [min.]: XXX.X

 

 

 

4.Enter the expected back-up time in min. at 100% ohmic (pf = 1) load, when the inverter has a mean efficiency of approx. 96%

Press I.e. 14.0 min.

5.Press to store data

6. Press or until

7 Press

to set Ah for battery

8.Press to store data

9.Press to exit

Expected back-up

time [min.]: 14.0

Data stored

Battery capacity

in [Ah]: XX.X

Battery capacity

in [Ah]: 7.0

Data stored

Normal operation load power XX%

Installation of new batteries:

When installing new batteries the procedure in section 4.4 MUST be carried out, otherwise the monitor may give false alarms.

7OA0004 US rev. 02