APC DP300E Series manual Programming example change charge voltage to

Models: DP300E Series

1 38
Download 38 pages 36.5 Kb
Page 19
Image 19

Programming Parameters

*For charge voltages, battery warnings and shut down voltages, and high battery temperature, the parameter is changed by entering the actual value like example 4.3.2.

NOTE:

Only for APC personnel and certified local APC personnel.

4.3.2 Programming example – change charge voltage to 446V*

Action

 

 

Display shows

1. Press

and

simultaneously to open

Key in password

:

 

 

for password input

 

 

 

2.Enter password xx xx xx by pressing

 

 

 

 

Last selected

 

 

 

 

parameter

3.

Press

or

until

Boost charge voltage

: 438

 

 

 

 

4.

Press

 

 

Boost charge voltage

 

 

: 446

5.

Press

to store

 

Data stored

 

 

6.

Wait about 1 second

 

Boost charge voltage

 

: 446

7.

Press

to exit

 

Normal operation

 

load power XX%

 

 

 

 

**The other parameters are

selected by pressing the key as step 4 in example 4.3.3. - one or more times.

4.3.3Programming example - change to output isolation transformer present**

Action

 

 

Display shows

1. Press

and

simultaneously to open

Key in password

 

 

for password input

:

 

 

 

2.Enter password xx xx xx by pressing

 

 

 

 

Last selected

 

 

 

 

parameter

3.

Press

or

until

Isolation trafo output

: NO

 

 

 

 

 

 

 

 

Isolation trafo output

4.

Press

for change

: YES

5.

Press

to store

 

Data stored

 

 

6.

Wait about 1 second

 

Isolation trafo output

 

: YES

 

 

 

 

7.

Press

to exit

 

Normal operation

 

load power XX%

 

 

 

 

 

 

 

 

7OA0004 US rev. 02

User Guide Silcon DP300E Series 480V 400-500kVA

19

Page 19
Image 19
APC DP300E Series manual Programming example change charge voltage to