Alarms
6.6Possible alarms
  | Possible alarm | Description | Action | |
  | 
  | 
  | 
  | 
  | 
  | 1.  | Peak current limiter active  | Peak current limiter has  | Check for blown  | 
  | 
  | 
  | been activated and UPS  | fuses in your  | 
  | 
  | 
  | switched to bypass opera-  | installation  | 
  | 
  | 
  | tion. System overloaded  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 2.  | Bypass power supply fault  | Fault in redundant PSU  | Call for assistance  | 
  | 
  | 
  | for bypass. UPS has still  | 
  | 
  | 
  | 
  | 100% performance and can  | 
  | 
  | 
  | 
  | operate in all modes  | 
  | 
  | 3.  | Delta current limiter active  | Input current limiter has  | Check for overload.  | 
  | 
  | 
  | been activated and UPS  | If repetitiv – call for  | 
  | 
  | 
  | switched to bypass opera-  | assistence  | 
  | 
  | 
  | tion  | 
  | 
  | 4.  | Fan fault  | Blocked or faulty fan  | Remove blocking or  | 
  | 
  | 
  | 
  | call for assistance  | 
  | 
  | 
  | 
  | 
  | 
  | 5.  | High DC warning  | Switching off big output load  | If repetitive reduce the  | 
  | 
  | 
  | 
  | load change  | 
  | 6.  | High DC shutdown  | Fault in UPS  | Call for assistance  | 
  | 7.  | Off button pushed  | Off button or emergency  | –  | 
  | 
  | 
  | power down activated  | 
  | 
  | 8.  | Synchronization error  | The UPS can’t synchronize  | Check if phase  | 
  | 
  | 
  | to the input frequency  | rotation of main input  | 
  | 
  | 
  | 
  | voltage is correct – if  | 
  | 
  | 
  | 
  | OK call for assistance  | 
  | 9.  | Inverter voltage error  | Inverter average voltage out  | –  | 
  | 
  | 
  | of limits (normal message  | 
  | 
  | 
  | 
  | during starting up/switching  | 
  | 
  | 
  | 
  | off the system)  | 
  | 
  | 10.  | Parallel sync. error  | Parallel UPS’s are not able  | Check external  | 
  | 
  | 
  | to synchronize  | parallel cables  | 
  | 
  | 
  | 
  | Call for assistance  | 
  | 11.  | Inverter current limiter  | Overload on inverter  | Reduce UPS output  | 
  | 
  | active  | 
  | load  | 
  | 12.  | Overload Load is over  | Overload on UPS  | Reduce UPS output  | 
  | 
  | 100%  | 
  | load  | 
  | 13.  | Second power supply fault  | Fault in UPS  | Call for assistance  | 
  | 
  | 
  | (Only in systems >160kW)  | 
  | 
  | 14.  | Internal power supply fault  | Fault in UPS. Only bypass  | Call for assistance  | 
  | 
  | 
  | operation possible  | 
  | 
  | 15.  | Battery MCB is off  | Battery MCCB switch not  | Close MCCB.  | 
  | 
  | 
  | closed or released.  | If released again  | 
  | 
  | 
  | 
  | – call for assistance  | 
  | 16.  | ** Q004 off **  | Position of output switch for  | –  | 
  | 
  | 
  | UPS in parallel  | 
  | 
  | 17.  | ** Q003 on **  | Position of external bypass  | –  | 
  | 
  | 
  | switch  | 
  | 
  | 18.  | ** Q002 off **  | Position of UPS output  | –  | 
  | 
  | 
  | switch  | 
  | 
  | 19.  | ** Q001 or Q010 off **  | Position of UPS input switch  | –  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 7OA0004 US rev. 02  | 
  | 
  | 
  | 
  | 
  | 
User Guide Silcon DP300E Series 480V  | 27  |