Alarms

NOTE:

Utility = Mains

7OA0004 US rev. 02

Possible alarm

Description

Action

 

 

 

 

20.

High temp. isolation

Temperature on isolation

Check fan, check for

 

transformer

input/output transformer to

airflow obstructions,

 

 

high

check for overload

21.

High temp. utility static

Temperature on static input

As no. 20

 

switch

switch too high

 

22.

High temp. bypass static

Temperature on static bypass

As no. 20

 

switch

switch too high

 

23.

High temperature main

Temperature on main inverter

As no. 20

 

inverter

too high

 

24.

High temperature delta

Temperature on delta inverter

As no. 20

 

inverter

too high

 

25.

Low DC shutdown

The battery has been

Ensure battery

 

 

discharged to minimum

recharging

 

 

permissionable level

 

26.

Low DC warning

The battery is nearly

Save your data now

 

 

decharged

Power down equip-

 

 

 

ment

27.

Mains is moment. out of

Short disturbances on the

 

tolerance

utility supply (1 ms tran-

 

 

 

sients)

 

28.

Mains is out of tolerance

Utility input voltage r.m.s.

 

 

value outside limits

 

29.

Mains freq. is out of

Utility input frequency outside

 

tolerance

limits

 

30.

Bypass is moment out of

Short disturbances on the

 

tolerance

bypass voltage

 

31.

Bypass is out of tolerance

Bypass input voltage outside

 

 

limit

 

32.

Bypass freq. is out of

Bypass input frequency

 

tolerance

outside limits

 

33.

Output is moment. out of

Short disturbances on the

If repetitive call for

 

tolerance

output voltages

assistance

 

 

(inrush current)

 

34.

Output is out of tolerance

Output voltage outside limits

Call for assistance

 

 

 

 

35.

Output freq. is out of

Output frequency outside

Call for assistance

 

tolerance

limits

 

36.

High battery temperature

To high battery ambient

Check system

 

 

temperature

ambient temp., check

 

 

 

fan, check for airflow

 

 

 

obstructions

 

 

 

 

37.

Battery week

Battery capacity below 75%

Perform a battery

 

 

or battery MCCB switched off

capacity test

 

 

 

 

38.

Battery defective

Insufficient battery capacity

Call for assistance

 

 

or battery MCCB switched off

 

 

 

 

 

28

User Guide Silcon DP300E Series 480V 400-500kVA

Page 28
Image 28
APC DP300E Series manual Temperature on static bypass