4
Specifications
Input Voltage
Operation Voltage Range
Power Consumption
Memory Protection
Display Method
Sensor Type
Control Mode
Control Output
Display Accuracy
Sampling Rate
Vibration Resistance
Shock Resistance
Ambient Temperature
Storage Temperature
Altitude
Relative Humidity
100 to 240VAC 50/60Hz
85% to 110% of rated voltage 5VA max.
EEPROM 4K bit
2 line x 4 character
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
Analog input: 0~5V, 0~10V, 0~ 20 m A, 4~20 m A, 0~50mV
PID, ON/OFF, Manual or PID program control (Ramp/Soak control)
Relay output: SPDT (SPST: 1/16 DIN and 1/32 DIN size), Max. load 250VAC, 5A resistive load
Voltage pulse output: DC 14V, Max. output current 40mA
Current output: DC 4 ~ 20m A output (Load resistance: Max. 600Ω)
Linear voltage output: 0~5V, 0~10V
0 or 1 digit to the right of the decimal point (selectable)
Analog input: 150 msec/ per scan Thermocouple or Platinum RTD: 400 msec/per scan MODBUS ASCII / RTU communication protocol
10 to 55Hz, 10m/s2 for 10min, each in X, Y and Z directions Max. 300m/ s2, 3 times in each 3 axes, 6 directions
0 oC to +50 oC
35% to 80%
5
Temperature Sensor Type and Temperature Range
Input Temperature Sensor Type | Register Value | LED Display | Temperature Range | |||
0~50mV Analog Input | 17 |
|
|
| ||
|
|
|
|
|
| |
4~20mA Analog Input | 16 |
|
|
| ||
|
|
|
|
|
| |
0~20mA Analog Input | 15 |
|
|
| ||
|
|
|
|
|
| |
0V~10V Analog Input | 14 |
|
|
| ||
|
|
|
|
|
| |
0V~5V Analog Input | 13 |
|
|
| ||
|
|
|
|
|
| |
Platinum Resistance (Pt100) | 12 |
|
|
| ||
|
|
|
|
|
|
|
Platinum Resistance (JPt100) | 11 |
|
|
| ~ 400oC | |
|
|
|
|
|
| |
Thermocouple TXK type | 10 |
|
|
| ||
|
|
|
|
|
| |
Thermocouple U type | 9 |
|
|
| ||
|
|
|
|
|
| |
Thermocouple L type | 8 |
|
|
| ||
|
|
|
|
|
| |
Thermocouple B type | 7 |
|
|
| 100 ~ 1800oC | |
|
|
|
|
|
| |
Thermocouple S type | 6 |
|
|
| 0 ~ 1700oC | |
|
|
|
|
|
| |
Thermocouple R type | 5 |
|
|
| 0 ~ 1700oC | |
|
|
|
|
|
|
|
Thermocouple N type | 4 |
|
|
| ~ 1300oC | |
|
|
|
|
|
| |
Thermocouple E type | 3 |
|
|
| 0 ~ 600oC | |
|
|
|
|
|
| |
Thermocouple T type | 2 |
|
|
| ||
|
|
|
|
|
|
|
Thermocouple J type | 1 |
|
|
| ~ 1200oC | |
|
|
|
|
|
|
|
Thermocouple K type | 0 |
|
|
| ~ 1300oC |
Note 1 : An external 250Ω precision resistor should be connected when the current input is selected as the input temperature sensor type..
Note 2 : (Operation mode) must be set if user wish to specify decimal point position. Except for the thermocouple B, S, R type, the decimal point positions of all the other thermocouple type input sensors can be set.
The default range of analog input is
2