B&B Electronics DTB Series user manual Alarm Outputs, Alarm Type, Alarm Output Operation

Models: DTB Series

1 13
Download 13 pages 49.76 Kb
Page 7
Image 7
Alarm Outputs

Alarm TypeAlarm Output Operation 8 Manual backgroundManual background

Alarm Outputs

There are up to three groups of alarm outputs and each group allows thirteen alarm types in the initial setting mode. The alarm output is activated whenever the process temperature value (PV) is getting higher or lower than the set point of alarm limit.

Set

Alarm Type

 

Alarm Output Operation

Value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

Alarm function disabled

Output is OFF

 

 

 

 

 

 

 

 

 

 

 

1

Deviation upper- and lower-limit:

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates when PV value is higher than the setting value SV+(AL-H) or lower than the OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setting value SV-(AL-L).

SV-(AL-L) SV

SV+(AL-H)

2

Deviation upper-limit:

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates when PV value is higher than the setting value SV+(AL-H).

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV

SV+(AL-H)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Deviation lower-limit:

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates when PV value is lower than the setting value SV-(AL-L).

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV-(AL-L) SV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Reverse deviation upper- and lower-limit:

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates when PV value is in the range of the setting value SV+(AL-H) and the setting OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

value SV-(AL-L).

SV-(AL-L) SV

 

SV+(AL-H)

5

Absolute value upper- and lower-limit:

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates when PV value is higher than the setting value AL-H or lower than the setting

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

value AL-L.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L

 

AL-H

6

Absolute value upper-limit:

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates when PV value is higher than the setting value AL-H.

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

Absolute value lower-limit:

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates when PV value is lower than the setting value AL-L.

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

Deviation upper- and lower-limit with standby sequence:

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates when PV value reaches set point (SV value) and the value is higher than the OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setting value SV+(AL-H) or lower than the setting value SV-(AL-L).

SV-(AL-L) SV

 

SV+(AL-H)

9

Deviation upper-limit with standby sequence:

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates when PV value reaches set point (SV value) and the reached value is higher OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV

 

 

 

 

 

 

 

 

 

 

 

 

than the setting value SV+(AL-H).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV+(AL-H)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

Deviation lower-limit with standby sequence: this alarm output operates when PV value reaches the set

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

point (SV value) and the reached value is lower than the setting value SV-(AL-L).

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV-(AL-L) SV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

Hysteresis upper-limit alarm output:

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates if PV value is higher than the setting value SV+(AL-H). This alarm output is OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF when PV value is lower than the setting value SV+(AL-L).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L AL-H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

Hysteresis lower-limit alarm output:

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates if PV value is lower than the setting value SV-(AL-H). This alarm output is OFF OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

when PV value is higher than the setting value SV-(AL-L).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-H AL-L

13

CT alarm output:

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm operates when the current measured by transformer (CT) is lower than AL-L or higher than OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-H (This alarm output is available only for the controller with current transformer).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL-L SV

 

 

AL-H

14When program control is end status, alarm output is ON.

15When RAMP UP status happens to PID program control, alarm output is ON.

16When RAMP DOWN status happens to PID program control, alarm output is ON.

17When SOAK status happens to PID program control, alarm output is ON.

18When RUN status happens to PID program control, alarm output is ON.

Note: AL-H and AL-L include AL1H, AL2H, AL3H and AL1L, AL2L, AL3L

6

Page 7
Image 7
B&B Electronics DTB Series user manual Alarm Outputs, Alarm Type, Alarm Output Operation