B&B Electronics DTB Series Current Transformer CT Function, EVENT Inputs Function, PID Control

Models: DTB Series

1 13
Download 13 pages 49.76 Kb
Page 8
Image 8
Current Transformer (CT) Function

EVENT Inputs FunctionPID Program Control (Ramp/Soak Program Control) 9 Description of Function and Parameters Setting:PID Control

Current Transformer (CT) Function

The Current Transformer (CT) function is used with the alarm output. When using a current transformer (CT) with the controller, change the corresponding alarm output mode to mode 13 (alarm output set value is 13), then turn to operation mode and set the current lower-limit and current upper-limit. You can set current alarm range between 0.5A ~ 30A, display resolution is 0.1A and measure accuracy is +/- 0.5A.

Valve Control:Manual background 10 Manual backgroundManual background

5

EVENT Inputs Function

There are two optional event inputs (contact inputs) supported (EVENT1and EVENT2) in DTB series.

EVENT1: RUN/STOP operation can be executed by RUN/STOP parameters (Operation Mode) or via the communication. User also can control RUN/STOP operation by EVENT 1 in DTB series. The control output is ON if the circuit of EVENT 1 is open when the controller is operating. Otherwise, the controller will stop output if the circuit of EVENT 1 is short or when the system parameter of the controller is set to STOP mode.

EVENT2: DTB series allows user can switch two temperature setting value by changing the status (open/short) of EVENT 2. Each temperature setting value has independent control parameters.

Manual backgroundManual background 11 Manual backgroundManual background

PID Program Control (Ramp/Soak Program Control)

Description of Function and Parameters Setting:

PID program control by 8 patterns (Pattern No. 0~7) is supported in DTB series. Each pattern contains 8 steps (step No. 0 ~ 7), one Link Pattern parameter, one Cycle parameter and one Actual Step parameter.

Start Pattern: Manual background is in operation mode and it is used to set the Start Pattern of PID program control (This parameter appear in mode only).

Steps : Include set point X and execution time T, these two parameters setting. The set point (SV) should reach temperature X after the period of execution time T. If the set point is the same as the result of the previous setting, then it is called Soak program control. If not, then it is called Ramp program control. Therefore, PID program control is also called Ramp/Soak program control. The default of step No. 0 in this controller is Soak program control. The controller will control the temperature (PV) to reach the set point X and then keep the temperature at set point X. The period of execution time is time T which provided by step No. 0.

Link Pattern Parameter : For example, when set Manual background to 2, it indicates that pattern No. 2 will execute next after the execution of pattern No.

0.If set to Manual background , it indicates the program will stop after executing the current pattern and the temperature will keep at the set point of the last step.

Cycle Parameter : Additional execution cycle number. For example, when set Manual background to 2, it indicates that pattern No. 4 should execute twice in addition. Include origin one time execution, total execute three times.

Actual Step Parameter : Execution step number per pattern (can set to 0 ~ 7). For example, when set Manual background to 2, it indicates that pattern No 7 will not execute other steps than step 0 to step2.

Execution : When Manual background is set to Manual background , the program will start to execute in order from the step 0 of start pattern. When Manual background is set to

Manual background , the program will stop and the control output is disabled. When Manual background is set to Manual background , the program will stop and the temperature

at that time will be controlled at the set point before program stop. Select Manual background again, then the program will restart and execute from

step 0 of start pattern. When Manual background is set to Manual background , the program will hold and the temperature at that time will be controlled at the set

point before program hold. Select Manual background again, then the program will follow the step before hold and start to execute through the rest of the time.

Display : During PID program control, the SV default display is P-XX, P indicates the current execution pattern and XX indicates the current

execution step. Press Manual backgroundManual background to change the display item. After select Manual background , press Manual background key, and then the temperature set point of the

current execution step will display on SV display. After select Manual background , press Manual background key, and then the residual time of the current execution step will display on SV display.

Manual backgroundManual background 12 Manual backgroundManual background

PID Control

One group can be selected from any one of 4 groups PID parameters (P, I, D, IOF) for PID control. After AT, PID value and temperature setting

will be stored in the selected one group. Manual background ~ Manual background : PIDn, n=0~4 from which 0~3 correspond to each PID parameter. Manual background : n=4, auto PID parameter. Program will automatically select a most useful PID parameter based on current temperature setting. Displayed SV values

correspond to Manual background ~ Manual background

Manual background ~ Manual background : Temperature setting corresponded to the selected PID parameter via user-defined or AT.

Valve Control:

When use valve control as output control, there are 2 Relay outputs for motor forward/reverse control, one (output 1) for valve open the other (output 2) for valve close. The output volume is controlled by valve open/close and it can be set with feedback function enabled or disabled. When feedback is disabled, output 1 will keep output while valve fully opens and output 2 will keep output while valve fully closes. But if feedback is enabled, please follow the parameter setting for valve control as follows:

Manual background : Time for valve from full close to full open.

Manual background : Dead Band setting of valve. The value of current valve output minus previous one must be greater than Dead Band value; otherwise, valve will remain OFF.

Manual background : Signal feedback setting, ON for enabling feedback and OFF for disabling feedback.

When Manual background set to ” 1”, it means signal feedback function is activated and will come up selections as follows:

a.Manual background : Upper/Lower limit of valve feedback by auto-tuning. Manual background must set to Manual background for showing up this selection.

b.Manual background : D/A value when value fully opens. Set Manual background to be ”1” for auto setting or ”0” for manual setting.

c.Manual background : D/A value when value fully closes. Set Manual background to be ”1” for auto setting or “0” for manual setting.

Note: If feedback function setting is with problem, program will see the setting as feedback disabled.

7

Page 8
Image 8
B&B Electronics DTB Series user manual Current Transformer CT Function, EVENT Inputs Function, PID Control, Valve Control