B&B Electronics DTB Series user manual RS-485 Communication, Address, 100AH, 101AH, 102AH

Models: DTB Series

1 13
Download 13 pages 49.76 Kb
Page 9
Image 9
RS-485 Communication
8

Address100AH 13 Proportional control offset error value,101AH

RS-485 Communication

1.Supporting transmission speed: 2400, 4800, 9600, 19200, 38400bps

2.Non-supported formats: 7, N, 1 or 8, O, 2 or 8, E, 2

3.Communication protocol: Modbus (ASCII or RTU)

4.Function code: 03H to read the contents of register (Max. 8 words). 06H to write 1 (one) word into register. 02H to read the bits data (Max. 16 bits). 05H to write 1 (one) bit into register.

5.Address and Content of Data Register:

Address

Content

Explanation

 

 

Measuring unit is 0.1, updated one time in 0.4 second

 

 

The following reading value display indicates error occurs:

1000H

Process value (PV)

8002H : Initial process (Temperature value is not got yet)

8003H : Temperature sensor is not connected

 

 

8004H : Temperature sensor input error

 

 

8006H : Cannot get temperature value, ADC input error

 

 

8007H : Memory read/write error

1001H

Set point (SV)

Unit is 0.1, oC or oF

1002H

Upper-limit of temperature range

The data content should not be higher than the temperature range

1003H

Lower-limit of temperature range

The data content should not be lower than the temperature range

1004H

Input temperature sensor type

Please refer to the contents of the “Temperature Sensor Type and Temperature Range” for detail

1005H

Control method

0: PID, 1: ON/OFF, 2: manual tuning, 3: PID grogram control

1006H

Heating/Cooling control selection

0: Heating, 1: Cooling, 2: Heating/Cooling, 3: Cooling/Heating

1007H

1st group of Heating/Cooling control

0~99, 0:0.5 sec

 

cycle

0~99, 0:0.5 sec

1008H

2nd group of Heating/Cooling control

 

cycle

0.1 ~ 999.9

1009H

PB Proportional band

100AH

Ti Integral time

0~9999

100BH

Td Derivative time

0~9999

100CH

Integration default

0~100%, unit is 0.1%

100DH

Proportional control offset error value,

0~100%, unit is 0.1%

 

when Ti = 0

0.01 ~ 99.99

100EH

The setting of COEF when Dual Loop

 

output control are used

-999 ~ 9999

100FH

The setting of Dead band when Dual

 

Loop output control are used

0 ~ 9999

1010H

Hysteresis setting value of the 1st

 

output group

0 ~ 9999

1011H

Hysteresis setting value of the 2nd

 

output group

Unit is 0.1%, write operation is valid under manual tuning mode only.

1012H

Output value read and write of Output

 

1

Unit is 0.1%, write operation is valid under manual tuning mode only.

1013H

Output value read and write of Output

 

2

1 Unit = 2.8uA(Current Output) = 1.3mV(Linear Voltage Output)

1014H

Upper-limit regulation of analog linear

 

output

1 Unit = 2.8uA(Current Output) = 1.3mV(Linear Voltage Output)

1015H

Lower-limit regulation of analog linear

 

output

-999~+999, unit: 0.1

1016H

Temperature regulation value

1017H

Analog decimal setting

0 ~ 3

1018H

Time for valve from full open to full

0.1~999.9

 

close

0~100%; unit: 0.1%

1019H

Dead Band setting of valve

101AH

Upper-limit of feedback signal set by

0~1024

 

valve

0~1024

101BH

Lower-limit of feedback signal set by

 

valve

0~4

101CH

PID parameter selection

101DH

SV value corresponded to PID value

Only valid within available range, unit: 0.1 scale

1020H

Alarm 1 type

Please refer to the contents of the “Alarm Outputs” for detail

1021H

Alarm 2 type

Please refer to the contents of the “Alarm Outputs” for detail

1022H

Alarm 3 type

Please refer to the contents of the “Alarm Outputs” for detail

1023H

System alarm setting

0 : None (default), 1~3 : Set Alarm 1 to Alarm 3

1024H

Upper-limit alarm 1

Please refer to the contents of the “Alarm Outputs” for detail

1025H

Lower-limit alarm 1

Please refer to the contents of the “Alarm Outputs” for detail

1026H

Upper-limit alarm 2

Please refer to the contents of the “Alarm Outputs” for detail

1027H

Lower-limit alarm 2

Please refer to the contents of the “Alarm Outputs” for detail

1028H

Upper-limit alarm 3

Please refer to the contents of the “Alarm Outputs” for detail

1029H

Lower-limit alarm 3

Please refer to the contents of the “Alarm Outputs” for detail

102AH

Read LED status

b0 : Alm3, b1: Alm2, b2: F, b3: oC, b4: Alm1, b5: OUT2, b6: OUT1, b7: AT

102BH

Read pushbutton status

b0 : Set, b1 : Select, b2 : Up, b3 : Down. 0 is to push

102CH

Setting lock status

0 : Normal, 1 : All setting lock, 11 : Lock others than SV value

102DH

CT read value

Unit: 0.1A

102FH

Software version

V1.00 indicates 0x100

Page 9
Image 9
B&B Electronics DTB Series RS-485 Communication, Address, 100AH, Proportional control offset error value, 101AH, 102AH