Hi RES Parameters

Level 1, Input Setup Block

Parameter

P#

Adjustable Range

Factory

User Setting

COMMAND

1402

3-KEYP AD

1

 

SOURCE

 

4-NETWORK

 

 

 

 

5- Opt1 Ana In1

 

 

 

 

6- Opt1 Ana In2

 

 

 

 

7- Opt2 Ana In1

 

 

 

 

8- Opt2 Ana In2

 

 

 

 

9-EXB PULSE FOLL

 

 

OP1 ANA IN1

1451

0-None, 1-(-10V to+10V),

1

 

TYPE

 

2-(-5V to+5V),

 

 

 

 

3-(4to20mA), 4-(0to20mA)

 

 

 

 

 

 

 

OP1 ANA IN1

1452

0-OFF, 1-ON

0

 

Invert

 

 

 

 

 

 

 

 

 

OP1 ANA IN1

1453

0.0% TO 300.0%

100.0

 

Gain

 

 

 

 

 

 

 

 

 

OP1 ANA IN1

1454

-100.0% TO 100.0%

0.0

 

Offset

 

 

 

 

 

 

 

 

 

OP1 ANA IN1

1455

0.0% TO 75.0%

0.0

 

Deadband

 

 

 

 

 

 

 

 

 

OP1 ANA IN1

1456

0 (No Filter) TO 6 (Max Filter)

0

 

Filter

 

 

 

 

 

 

 

 

 

OP1 ANA IN2

1457

0-None, 1-(-10V to+10V),

1

 

TYPE

 

2-(-5V to+5V),

 

 

 

 

3-(4to20mA), 4-(0to20mA)

 

 

 

 

 

 

 

OP1 ANA IN2

1458

0-OFF, 1-ON

0

 

Invert

 

 

 

 

 

 

 

 

 

OP1 ANA IN2

1459

0.0% TO 300.0%

100.0

 

Gain

 

 

 

 

 

 

 

 

 

OP1 ANA IN2

1460

-100.0% TO 100.0%

0.0

 

Offset

 

 

 

 

 

 

 

 

 

OP1 ANA IN1

1461

0.0% TO 75.0%

0.0

 

Deadband

 

 

 

 

 

 

 

 

 

OP1 ANA IN1

1462

0 (No Filter) TO 6 (Max Filter)

0

 

Filter

 

 

 

 

OP1 parameter selections (P#1451 to 1462) are available if the expansion board is installed in Slot1 of the Control.

4‐2 Setup

Page 16