Figure 17 (continued) - 7600A/B alternate multi-zone connections with Indirect Domestic Hot Water (DHW)

*Additional zones can be added by duplicating the plumbing and wiring of zone 3, adding additional transformers as needed.

CONTINUED FROM PREVIOUS PAGE

Control Wiring (Option 2): 7600A only

1.Set “DHWP on ZR” (see programming section for instructions)

2.Set “C1 on BOTH” (see programming section for instructions)

3.Circulator-on delay will affect all zones. Circulator-off delay will have no effect.

4.24 VAC zone valves cannot be powered directly with the 7600A. Add an additional transformer as shown for every two or less valves.

5.Ensure there are no jumpers between the terminals of the zone valves.

DHW ZONE 24 VAC ZONE VALVE

Honeywell

V8043F

TR TH

MTR

ZONE 1

LOW VOLTAGE

THERMOSTAT

ZONE 1

24 VAC ZONE VALVE

Honewell

V8043F

SK10047

TR

TH

TH/

 

 

TR

 

 

 

MTR

TW

TR

 

L2 L1

C1 C2 ZC ZR B1 B2

NEUTRAL WHITE

120 VAC

BURNER OR

 

 

120 VAC

BLACK

GAS IGNITION

 

SYSTEM

HOT FIELD/MFR.

 

SUPPLIED

 

SERVICE

 

SWITCH

 

 

 

40 VA

 

 

TRANSFORMER

GENERAL

CIRCULATOR

CIRCULATOR

120 VAC

ZONE 3*

LOW VOLTAGE

THERMOSTAT

ZONE 3*

24 VAC ZONE VALVE

Honewell

V8043E, V8044E

TH/

Y

MTR

Y

TR

 

 

 

RR

ZONE 2

LOW VOLTAGE

THERMOSTAT

ZONE 2

24VAC ZONE VALVE

Taco 550

1

MTR

32

6ZONE RELAY

5

4DHW LIMIT

3CONTROL

2/N T

1/H T

40 VA TRANSFORMER

24

Page 24
Image 24
Beckett 7600 manual Taco