Table 1b (continued from previous page)

Honeywell

Beckett

Replacement

Notes

L4081A/B

L6081A/C

7600A or 7600B (Based on System Voltage Requirements)

Remove switching relay, if used, from the system when replacing the L4081 or L6081.

Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.

L6006A (All) L6006C 1018 L6008A 1192 L6008A 1242

7600A or 7600B (Based on System Voltage Requirements)

Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600.

To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the millivolt circuit. Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.

7600 will require an additional wire (L2) for operation. Short TW-TRterminals. C1, C2, ZC, and ZR are unused. Set low limit on 7600 to OFF.

Available operating limit and/or differential ranges may not be equivalent. Compare the settings to the AquaSmart ranges before replacing.

L8124B 1039 L8148J 1009

7600A or 7600B (Based on System Voltage Requirements)

To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the millivolt circuit. 7600 outputs are not rated for 240 VAC.

Carlin

Beckett

Replacement

Notes

90200A

7600A or 7600B (Based on System Voltage Requirements)

Make sure 7600 outputs do not exceed 7.4A. Set low limit on 7600 to OFF.

Available operating limit and differential ranges are not equivalent. Compare the settings to the AquaSmart ranges before replacing.

90000 (All)

90200E

90200EL

90300B

7600A or 7600B (Based on System Voltage Requirements)

Requires the addition of a manual-reset high limit. Make sure 7600 outputs do not exceed 7.4A.

Set low limit on 7600 to OFF.

Available operating limit and differential ranges are not equivalent. Compare the settings to the AquaSmart ranges before replacing.

90200D

7600A or 7600B (Based on System Voltage Requirements)

Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600. Make sure 7600 outputs do not exceed 7.4A.

Set low limit on 7600 to OFF.

Available operating limit and differential ranges are not equivalent. Compare the settings to the AquaSmart ranges before replacing.

White Rodgers

Beckett

Replacement

Notes

11B06-1

11D18-1

11B18-101

11B30-104

11B02-1

1145-33

7600A or 7600B (Based on System Voltage Requirements)

Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.

7600 will require an additional wire (L2) for operation. Short TW-TRterminals. C1, C2, ZC, and ZR are unused. Set low limit on 7600 to OFF.

11B06-46

11B95-31

11B18-153

7600A or 7600B (Based on System Voltage Requirements)

Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.

7600 will require an additional wire (L2) for operation. Short TW-TRterminals. C1, C2, ZC, and ZR are unused. Set low limit on 7600 to OFF.

Available operating limit and/or differential ranges are not equivalent. Compare the settings to the AquaSmart ranges before replacing.

11D82-1

11D31-1

1131-102

1127-2

11A79-2

7600A or 7600B (Based on System Voltage Requirements)

Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600.

7600 outputs are not rated for 240 VAC.

7600 will require an additional wire (L2) for operation. Short TW-TRterminals. C1, C2, ZC, and ZR are unused. Set low limit on 7600 to OFF.

1127-9

7600A or 7600B (Based on System Voltage Requirements)

Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600.

7600 outputs are not rated for 240 VAC.

7600 will require an additional wire (L2) for operation. Short TW-TRterminals. C1, C2, ZC, and ZR are unused. Set low limit on 7600 to OFF.

Available operating limit and/or differential ranges may not be equivalent. Compare the settings to the AquaSmart ranges before replacing.

11B27-9

7600A or 7600B (Based on System Voltage Requirements)

Requires the addition of a manual-reset high limit.

Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.

7600 will require an additional wire (L2) for operation. Short TW-TRterminals. C1, C2, ZC, and ZR are unused. Set low limit on 7600 to OFF.

Available operating limit and/or differential ranges are not equivalent. Compare the settings to the AquaSmart ranges before replacing.

8J48A-209

7600A or 7600B (Based on System Voltage Requirements)

To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the millivolt circuit.

6

Page 6
Image 6
Beckett 7600 manual From previous