Table 1b (continued from previous page)
Honeywell
Beckett
Replacement
Notes
L4081A/B
L6081A/C
7600A or 7600B (Based on System Voltage Requirements)
Remove switching relay, if used, from the system when replacing the L4081 or L6081.
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
L6006A (All) L6006C 1018 L6008A 1192 L6008A 1242
7600A or 7600B (Based on System Voltage Requirements)
Not a suitable replacement if SPDT switch action is required; only
To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the millivolt circuit. Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
7600 will require an additional wire (L2) for operation. Short
Available operating limit and/or differential ranges may not be equivalent. Compare the settings to the AquaSmart ranges before replacing.
L8124B 1039 L8148J 1009
7600A or 7600B (Based on System Voltage Requirements)
To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the millivolt circuit. 7600 outputs are not rated for 240 VAC.
Carlin
Beckett
Replacement
Notes
90200A
7600A or 7600B (Based on System Voltage Requirements)
Make sure 7600 outputs do not exceed 7.4A. Set low limit on 7600 to OFF.
Available operating limit and differential ranges are not equivalent. Compare the settings to the AquaSmart ranges before replacing.
90000 (All)
90200E
90200EL
90300B
7600A or 7600B (Based on System Voltage Requirements)
Requires the addition of a
Set low limit on 7600 to OFF.
Available operating limit and differential ranges are not equivalent. Compare the settings to the AquaSmart ranges before replacing.
90200D
7600A or 7600B (Based on System Voltage Requirements)
Not a suitable replacement if SPDT switch action is required; only
Set low limit on 7600 to OFF.
Available operating limit and differential ranges are not equivalent. Compare the settings to the AquaSmart ranges before replacing.
White Rodgers
Beckett
Replacement
Notes
7600A or 7600B (Based on System Voltage Requirements)
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
7600 will require an additional wire (L2) for operation. Short
7600A or 7600B (Based on System Voltage Requirements)
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
7600 will require an additional wire (L2) for operation. Short
Available operating limit and/or differential ranges are not equivalent. Compare the settings to the AquaSmart ranges before replacing.
7600A or 7600B (Based on System Voltage Requirements)
Not a suitable replacement if SPDT switch action is required; only
7600 outputs are not rated for 240 VAC.
7600 will require an additional wire (L2) for operation. Short
7600A or 7600B (Based on System Voltage Requirements)
Not a suitable replacement if SPDT switch action is required; only
7600 outputs are not rated for 240 VAC.
7600 will require an additional wire (L2) for operation. Short
Available operating limit and/or differential ranges may not be equivalent. Compare the settings to the AquaSmart ranges before replacing.
7600A or 7600B (Based on System Voltage Requirements)
Requires the addition of a
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
7600 will require an additional wire (L2) for operation. Short
Available operating limit and/or differential ranges are not equivalent. Compare the settings to the AquaSmart ranges before replacing.
7600A or 7600B (Based on System Voltage Requirements)
To use with a millivolt system an appropriate voltage relay with isolated gold plated contacts must be added to switch the millivolt circuit.
6