Beckett 7600 manual Installation, Sensor/Immersion Well Mounting Surface Mounting

Models: 7600

1 36
Download 36 pages 10.23 Kb
Page 4
Image 4

Figure 2 - Basic Dimensions (inches)

4.92

4.50

3.04

5.38

3.50

3.51

6.50

SK10013

.75

Installation

Mounting

OEM Installation: When replacing an OEM-installed AquaSmart, consult the appliance manufacturer’s wiring diagrams and instructions for additional information.

Retrofit Installation: The AquaSmart can be used to replace most standard boiler temperature controls. For a cross-reference of compatible replacements, refer to Table 1.

There are two basic methods for mounting the AquaSmart to the boiler as outlined in Figure 3.

1.Sensor/Immersion Well Mounting – This is the most common method. If the existing well is not suitable for any reason, a standard design aftermarket immersion well with the proper dimensions can be purchased from a HVAC distributor. The AquaSmart can then be mounted in the typical way.

2.Surface Mounting – This is sometimes required and is part of the AquaSmart base design. The base has adequate clearance built-in to accommodate the temperature sensor lead exiting the back of the control. A remote mounting kit (Pt. No. 7600RMU) that includes a 48” extension cable and mounting screws can be purchased separately for applications where needed.

Figure 3 - Mounting Options

Sensor/Immersion Well Mounting:

Surface Mounting:

Position the strain relief over the hex, capturing the sensor cable and crimp to secure.

Sensor Lead (a 48” extension cable can be purchased separately)

4

Page 4
Image 4
Beckett 7600 manual Installation, Sensor/Immersion Well Mounting Surface Mounting