Figure 14 (continued) - 7600A/B alternate multi-zone connections with or without a tankless coil

*Additional zones can be added by duplicating the plumbing and wiring of zone 3, adding additional transformers as needed.

CONTINUED FROM PREVIOUS PAGE

Control Wiring (Option 2): 7600A only

1.Set “DHWP OFF” (default, see programming section for instructions)

2.Set “C1 on TT” (default, see programming section for instructions)

3.Circulator-on delay will affect all zones. Circulator-off delay will have no effect.

4.24 VAC zone valves cannot be powered directly with the 7600A. Add an additional transformer for every two or less valves.

5.Ensure there are no jumpers between the terminals of the zone valves.

SK10046

TW

TR

 

L2 L1 C1 C2 ZC ZR B1 B2

NEUTRAL WHITE

 

120 VAC

BLACK

GENERAL

 

HOT FIELD/MFR.

CIRCULATOR

 

SUPPLIED

CIRCULATOR

 

SERVICE

120 VAC

 

SWITCH

 

 

ZONE 1

 

ZONE 2

 

 

ZONE 3*

 

LOW VOLTAGE

LOW VOLTAGE

 

LOW VOLTAGE

 

THERMOSTAT

THERMOSTAT

 

THERMOSTAT

ZONE 1

 

ZONE 2

 

ZONE 3*

 

 

24 VAC

 

24 VAC

 

24 VAC

 

 

ZONE VALVE

ZONE VALVE

 

ZONE VALVE

 

Taco

 

Honeywell

 

Honeywell

 

550

 

V8043E, V8044E

V8043F

 

 

 

1

Y MTR

Y

TR

TH

TH/

 

MTR

TR

 

 

 

MTR

 

 

 

 

 

 

 

 

 

3

2

R

R

 

 

 

40 VA TRANSFORMER

120 VAC

 

BURNER OR

40 VA

GAS IGNITION

TRANSFORMER

SYSTEM

 

16

Page 16
Image 16
Beckett manual Control Wiring Option 2 7600A only, Taco Honeywell