Blodgett KTT-E Series manual 5.0TROUBLESHOOTING 5.1GENERAL MAINTENANCE, 5.2LOW WATER LEVEL

Models: KTT-E Series

1 20
Download 20 pages 15.66 Kb
Page 11
Image 11

5.0TROUBLESHOOTING

5.1GENERAL MAINTENANCE

No general maintenance is required other than adhering to the Cleaning Procedure Instructions.

5.2LOW WATER LEVEL

Proper water level must be maintained within the jacket for the kettle to operate. Depletion of water may occur from excessive opening of, or leakage through the safety relief valve.

If water is below required operating level, either initially at start-up or during use, the kettle will automatically shut off, and the LOW WATER signal light will come on.

In order for the kettle to operate, the following procedure must be followed:

1.Trip the safety relief valve lever to relieve all pressure from the kettle jacket.

2.At exterior rear of kettle jacket remove nut from Air Vent.

3.Insert funnel into Air Vent opening and slowly add the indicated amount of distilled water for:

KTT-6E

Add 50 oz.

(1.5 litres)

KTT-10E and KTT-12E

Add 100 oz.

(3 litres)

4.Replace Air Vent nut.

5.Follow Air Venting Instructions below.

6.Continue normal Operating Procedure of kettle.

5.3VENTING INSTRUCTION

Check pressure gauge when kettle is cold. Gauge should be in the green vacuum zone. If not, air is present which must be vented (removed) for proper heating. Use the following procedures to vent air.

1.With an empty kettle, place power switch to the ON position.

2.Set temperature control thermostat to ‘10'. Heat kettle until heat indicator light goes off.

3.Using a 7/16" wrench, open bleed vent one full turn for 10 seconds and then close.

4.Cool kettle. Check for proper vacuum in the green vacuum zone. If reading is not low enough, repeat entire procedure.

11

Page 11
Image 11
Blodgett KTT-E Series manual 5.0TROUBLESHOOTING 5.1GENERAL MAINTENANCE, 5.2LOW WATER LEVEL, 5.3VENTING INSTRUCTION