•pin 4 and 7 for power good AC

AMC2 4W

Installing en 29

Fig. 5.6 Location of the power supply connector

An external power supply (10 - 30V DC) must be connected for internal electronics at pin 1 (positive) and pin 3 (negative) of the pluggable screw connector.

When using a shared 12V DC power supply for internal electron- ics and peripherals, pin 1 and pin 6 resp. pin 3 and pin 7 can be shortened.

If an uninterruptible power supply (UPS) is used, the relay out- put for power good signals from the UPS is connected to the following pins:

pin 4 and 7 for power good AC

pin 5 and 7 for power good Battery

pin 6 and 7 for power good DC Otherwise these pins must be short-circuited.