Keep in mind the following specifications.

42 en Installing

AMC2 4W

Fig. 5.19 Wet mode and dry mode of the AMC2 4W relay outputs

!

WARNING!

Keep in mind the following specifications.

 

For the protection of damage the relay keep in mind, that ...

– the maximum switching current is 1,25A

– the maximum switching voltage is 30V DC

– ohm resistive load can be connected to the relay, only

– inductive loads have to be short circuited using recovery diodes - see: Figure 5.20. These diodes (BAX12A) are sup- plied with every AMC2 4W package.

– If you need higher voltage for special constructions you can connect external relays to the outputs. Recommended, depending on the power supply mode, are the relay types of the company Wieland:

Flare move 12DC1W10A

Flare move 24DC1W16A

But you can also use products of manufacturer in your country - take care that the values of the product are iden- tical with the products listened above.

F.01U.024.965 V.4 2006.09