STEP7 (continued)
INSTALLINGTHE COOKTOP
NOTE: If the cooktop is installed in a 36" base
cabinet, the mounting brackets cannot be used
because of the interference with the sides of the cabinet. In this case, the cooktop can be secured to the sides of the cabinet using angle brackets
(not supplied). Remove one screw at the bottom of the cooktop body, on each side, then replace to hold the bracket to the cooktop. Then secure
the brackets to the cabinet sides with the screws provided.
Connect the
|
| |
Service Plate |
|
|
Electrical |
| Pressure |
|
| Test Point |
|
| ,Pressure |
Supply Cord | Regulator | |
Metal Cover |
|
Layout of Service Panel
STEP8
GASCONNECTION
Install the supplied pressure regulator and nipple in the gas line as close to the cooktop inlet
as possible, making allowances for
ventilation ducting as necessary.
Make sure the regulator is
installed in the right direction. Install a manual
the gas line in an easily accessible location, as close to the pipe stub
as possible, making allowances for
the ventilation ducting. Be sure you know how and where to shut off the gas supply to the cooktop.
NOTE: Instead of using solid piping to connect to pressure regulator, an approved flexible
metal appliance connector may be used between the pipe stub and
regulator, if local codes permit.
Appropriate flare union adapters are required at each end of the flexible connector.
Turn on the gas; check for leaks using a liquid leak detector at all joints in the system (the pressure
test nipple is adjacent to the gas inlet pipe on the rear right hand side of the cooktop bottom).
CAUTION: DO NOT USE A FLAME TO CHECK FOR GAS LEAKS.
piping system during any pressure testing of that
system at test pressures greater than 1/2 psig. Isolate the cooktop from the gas supply piping system by dosing the individual manual
valve to the cooktop during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig.
STEP9
INSTALLTHE DUCTWORK
Use minimum 26 gauge galvanized or 24 gauge aluminum duct in 6" round or 31/4"x 10" size, or a combination of both. PVC duct should be used
if installing under a poured concrete slab. DO NOT use flexible ducting.
Always use an
appropriate roof or wall cap with damper. Laundry
type wall caps should never be
used. Use the
straightest duct run possible.
For satisfactory
performance the duct run should not exceed
75 ft. or its equivalent length if bends or other various fittings are used. Refer to table of equivalent lengths for various duct configurations.
Install ductwork so that the piece of duct nearest the downdraft unit slots INTO the next piece of duct. Secure all joints with self tapping screws and apply duct tape around the joint to ensure an airtight seal.
(continued next page)
15