9.3 Troubleshooting Honeywell S8600 Intermittent Pilot System
Some boilers may be equipped with an ignition module that shuts off pilot gas if pilot fails to light.
Start
Turn off gas supply.
Turn thermostat
(controller) to call for
heat.
Power to module
(24V nominal).
YES
Spark across igniter/
sensor gap.
YES
Turn gas supply on. Pilot burner lights?
YES
Spark stops when pilot
is lit?
YES
Main burner lights?
YES
System runs until call
for heat ends?
YES
Call for heat ends. System shuts off?
YES Troubleshooting ends
To reset, interrupt power to heater
Note: Before troubleshooting, familiarize yourself with the
Check line voltage power, low voltage transformer, hi- limit switch, | |||||||
|
|
| NO | thermostat (controller) and wiring. | |||
|
|
|
|
|
| ||
|
|
|
|
|
| ||
|
|
|
| Pull ignition lead and check spark at module. |
| ||
|
|
| NO | Spark okay? |
| ||
|
|
| |||||
|
|
|
|
|
| ||
|
|
| |||||
|
|
| YES | ||||
|
|
|
|
|
|
| |
|
|
|
| • | Check ignition cable ground wiring, ceramic insulator and gap, and correct. | ||
|
|
|
| • | Check boot of the ignition cable for signs of melting or buckling. Take | ||
|
|
|
|
| protective action to shield cable and boot from excessive temperatures. | ||
|
|
|
|
|
| ||
|
|
| • | Check that all manual gas valves are open, supply tubing and pressures | |||
|
|
|
| are good, and pilot burner orifice is not blocked. | |||
|
| • | Check electrical connections between module and pilot operator on gas | ||||
|
|
| NO | ||||
|
|
|
| control. | |||
|
|
|
| • | Check for 24 Vac across | ||
|
|
|
| ||||
|
|
|
|
| okay, replace gas valve; if not, replace module. | ||
|
|
|
|
|
| ||
|
|
|
|
|
| ||
|
|
| NO | • | Check continuity of ignition cable and ground wire. | ||
|
|
| |||||
|
|
| • | Clean flame rod. | |||
|
| • | Check electrical connections between flame rod and module. | ||||
| |||||||
|
|
|
| • | Check for cracked ceramic flame rod insulator. | ||
|
|
|
| • | Check that pilot flame covers flame rod and is steady and blue. | ||
|
|
|
| • | Adjust pilot flame. | ||
|
|
|
| • | If problem persists, replace module. | ||
|
|
| |||||
|
|
| |||||
• | Check for 24 Vac across | ||||||
|
|
| NO | ||||
|
|
|
| module. | |||
|
|
|
| • | Check electrical connections between module and gas valve. If okay, | ||
|
|
|
| ||||
|
|
|
|
| replace gas valve. | ||
|
|
|
|
| |||
|
|
|
|
| |||
|
| • | Check continuity of ignition cable and ground wire. | ||||
| |||||||
|
|
| NO | ||||
|
|
|
| Note: If ground is poor or erratic, shutdowns may occur occasionally even | |||
|
|
|
|
| though operation is normal at the time of checkout. | ||
|
|
|
|
|
•Check that pilot flame covers flame rod and is steady and blue.
•If checks are okay, replace module.
|
|
| ||
• | Check for proper thermostat (controller) operation. | |||
| NO | |||
| • | Remove MV lead at module; if valve closes, recheck temperature | ||
|
| |||
|
|
| controller and wiring; if not, replace gas valve. | |
|
| Repeat procedure until |