Maximum Vent Length:

Direct Vent Maximum Vent Length (Combined Maximum Length for Intake and Exhaust)

Model Number

Max Vent

Max Vent

Max Vent

Length (feet) 2”

Length (feet) 3"

Length (feet) 4"

 

EF60T125, EF100T150

30

120

170

EF60T150, EF100T199

30

100

150

EF60T199

30

80

130

EF100T250

N/A

80

130

EF100T300

N/A

60

110

 

Table 3

 

 

Manual backgroundWARNING

The EF100T250 and EF100T300 models are not approved for 2 inch diameter vent pipe. Venting with 2 inch pipe on these models may result in damage to the water heater or cause an unsafe condition. DO NOT use 2 inch Vent or Air Intake Pipe on EF100T250/300 models.

Note: The venting distance shown in the chart above is the combined maximum distance for the intake and exhaust pipe and elbows. The intake and exhaust vent terminals may be in different locations (i.e., different walls or one wall, one roof) provided the intake equivalent venting distance does not exceed the exhaust by more than 30 feet.

Determining required vent length:

1.Determine the total length of straight vent pipe (in feet) required for both the intake and the exhaust.

2.Add 5 feet of venting for every 90° elbow.

3.Add 2 ½ feet of venting for every 45° elbow.

4.Total vent length cannot exceed “Max Vent Length” in Table 3.

5.Air intake cannot exceed exhaust by more than 30 feet in any venting situation.

Example of Total Direct Vent Length for EF100T199:

A 3” venting system has a total of six 90-degree elbows and a total straight pipe length of 65 feet (includes both intake and exhaust pipe).

Equivalent vent length for elbows: 6 x 5 feet = 30 feet.

Total equivalent vent distance = 65 feet + 30 feet = 95 feet total equivalent vent length. This is below the maximum allowed distance of 100 feet for this model using 3” vent.

NOTICE

Do not include the 3” condensate elbow or vent terminals in determining maximum vent length.