Bradford-White Corp 238-48384-00F warranty b. Direct Vent Terminal Clearances

Models: ULTRA HIGH EFFICIENCY COMMERCIAL GAS WATER HEATER 238-48384-00F

1 76
Download 76 pages 19.36 Kb
Page 22
Image 22
Figure 11b. Direct Vent Terminal Clearances

Figure 11b. Direct Vent Terminal Clearances

 

 

Canadian

US

 

 

Canadian

US Installations2

 

 

Installations1

Installations2

 

 

Installations1

 

 

 

 

 

 

 

3 feet (91 cm) within a

 

A=

Clearance above grade,

12 inches

12 inches

H=

Clearance to each side

*b

 

veranda, porch, deck or

(30 cm)

(30 cm)

 

of center line extended

height 15 feet (4.6 m)

 

 

balcony

 

 

 

above meter/regulator

above the

 

 

 

 

 

 

assembly

meter/regulator

 

 

 

 

 

 

 

assembly

 

B=

Clearance to window or

36 inches

12 inches

I=

Clearance to service

36 inches

*b

 

door that may be opened

(91 cm)

(30 cm)

 

regulator vent outlet or

(91 cm)

 

 

 

 

 

 

oil tank vent

36 inches

 

C=

Clearance to

*b

*b

J=

Clearance to non-

12 inches

 

permanently closed

 

 

 

mechanical air supply

(91 cm)

(30 cm)

 

window

 

 

 

inlet to building or the

 

 

 

 

 

 

 

combustion air inlet to

 

 

 

 

 

 

 

any other appliance

6 feet

 

D=

Vertical clearance to

12 inches

12 inches

K=

Clearance to a

3 feet (91 cm)

 

ventilated soffit located

(30 cm) *a

(30 cm) *a

 

mechanical air supply

(1.83 m)

above if within

 

above the terminal within

 

 

 

inlet

 

10 feet

 

a horizontal distance of 2

 

 

 

 

 

horizontally

 

feet (61 cm) from the

 

 

 

 

 

 

 

center line of the

 

 

 

 

 

 

 

terminal

 

 

 

 

7 feet

 

E=

Clearance to

12 inches

12 inches

L=

Clearance above paved

*b

 

unventilated soffit

(30 cm) *a

(30 cm) *a

 

sidewalk or paved

(2.13 m)†

 

 

 

 

 

 

driveway located on

 

 

 

 

 

 

 

public property

12 inches (30 cm) ‡

 

F=

Clearance to outside

*b

*b

M=

Clearance under a

12 inches (30

 

corner

 

 

 

veranda, porch, deck, or

 

cm) ‡

 

 

 

 

 

balcony

 

 

G=

Clearance to inside

36 inches

36 inches

 

 

 

 

 

corner

(91 cm)*a

(91 cm)*a

 

 

 

 

1In accordance with the current CAN/CGA-B149 Installation Codes.

2In accordance with the current ANSI Z223.1-(Latest Edition)/NFPA 54 National Fuel Gas Code.

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single-family dwellings and serves both dwellings.

‡ Permitted only if a veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. *a) A minimum clearance value determined by testing in accordance with section 2.20.

*b) “Clearance in accordance with local installation codes and the requirements of the gas supplier”.

22