Bradford-White Corp ULTRA HIGH EFFICIENCY COMMERCIAL GAS WATER HEATER Error, Definition of Code

Models: ULTRA HIGH EFFICIENCY COMMERCIAL GAS WATER HEATER 238-48384-00F

1 76
Download 76 pages 19.36 Kb
Page 69
Image 69

Error

Definition of Code

Cause of Problem and Actions Taken to Correct

Code

 

 

 

 

Burner is either not lighting or not staying lit during ignition cycle. Check inlet

 

 

gas pressure for minimum pressure on rating label. Can you hear sparking to

 

 

the burner? Check high voltage cable connections. Check inlet gas pressure

 

 

to the gas valve making sure the pressure is within the limits specified on the

 

 

rating label. Check gas valve wire harness for broken wires or shorts. Check

 

 

outlet gas pressure. If 24 volts is present to the terminals at the gas valve,

 

Maximum Number of

replace gas valve. Check for voltage output to the blue gas valve wires on the

62

control board pins. If during the ignition trial period, there is no voltage present

Retries Detected

 

at the control board pin terminals for the blue wires leading to the gas valve,

 

 

 

 

then replace the control board. Replace spark rod if insulator is damaged or

 

 

rod is loose. Check to make sure combustion blower is operating when

 

 

thermostat calls for heat. If blower is not running check for 120 volts to blower

 

 

harness and then at blower pin connections. Replace control, wire harness, or

 

 

blower if defective. Check to make sure vent terminals are clear of debris or

 

 

snow and ice. Make sure the condensate drain flows freely.

 

 

Burner flame is lost during run cycle, then re-established on ignition cycle.

 

 

Check inlet gas pressure. Is gas pressure dropping below the minimum

 

 

operating pressure on the rating label after the gas valve opens? Is the gas

 

Maximum Number of

pipe size to the water heater adequate? Check the condition of the burner.

63

Ignition Recycles

Clean or replace as needed. Check the burner flame and observe the

 

Detected

microamp output on the run cycle. Replace burner if clogged with dirt and

 

 

debris. Replace spark rod or flame sensor if damaged. Check to make sure

 

 

vent terminals are clear of debris or snow and ice. Make sure the condensate

 

 

drain flows freely.

64

Electronics Failure

Replace control board.

 

 

 

 

High Water

Water temperature in tank has exceeded 200°F (93°C). Check tank sensor.

 

Make sure sensor is fully inserted into the well (clip on sensor wire secures

65

Temperature (Over

sensor in place). Check sensor reading. If not within specifications, replace

 

200°F (93°C))

 

sensor. If sensor and wire harnesses check O.K., replace control board.

 

 

 

 

 

69

Page 69
Image 69