Remote Module LED Status Indicators

Symphony II System does not communicate or manage appliances/loads when utility power is present.

NOTICE When looking at LED’s, make sure you look straight on and not at an angle.

Low Voltage (Single and Dual) Models

A

C

B

ED

LED is for signal communication status (C).

Utility power present:

Normal State

-Orange LED - No communication and appliances/ loads cannot be managed by Symphony II System

Problem State (see Troubleshooting)

-No LED - No power to low voltage control board; verify correct wiring

-Green LED - Broken LED; replace low voltage module

-Red LED - Fault in system; verify current transformer connections, verify terminations on orange and yellow communication wires

Generator power present:

Normal State

-Green LED - Signal communication detected and appliances/loads can be managed after

5 minute delay

Problem State (see Troubleshooting)

 

 

 

- No LED - No power to low voltage control board;

 

 

REPRODUCTION

 

 

 

verify correct wiring

 

 

 

- Orange LED - Signal communication not detected;

A - Low Voltage Control Wiring Terminal Contacts

verify correct wiring

B - Priority Selector

 

 

- Red LED - Fault in system; verify current

 

 

transformer connections, verify terminations on

C - Communication LED

 

 

orange and yellow communication wires

D - Neutral Connection

NOT

 

 

E - Power/Line Connection

 

 

 

 

FOR

 

18

BRIGGSandSTRATTON.COM