Troubleshooting

Problem

 

Cause

Correction

Automatic transfer switch does

 

1.Generator breaker open.

1.Reset generator circuit breaker.

not transfer to generator

 

2.Generator voltage not acceptable.

2.Refer to generator manual.

 

 

3.Generator disconnect circuit breaker open

3.Reset generator disconnect circuit

 

 

in transfer switch.

breaker in transfer switch.

Automatic transfer switch does

 

1.Utility disconnect circuit breaker open in

1.Reset utility disconnect circuit breaker

not transfer to utility

 

transfer switch.

in transfer switch.

 

 

2.Utility voltage not acceptable.

2.Wait for utility voltage to return

 

 

 

to normal.

Generator is still running after

 

Engine cool down period.

Engine should stop after 1 minute.

switch transfers to utility

 

 

 

power

 

 

 

Generator or supervised loads

 

1.Remote modules are not

1.Five minute delay timer has

(air conditioner, etc..) are

 

operating correctly.

not expired.

operating improperly when

 

2.Too much load on generator.

2.Decrease load to generator.

generator is supplying power

3.Current transformer not connected.

3.Contact local authorized service center.

 

 

4.Broken current transformer.

4.Contact local authorized service center.

 

 

5.Communication lost due to power line

5.Verify fluorescent ballasts are rated for

 

 

noise.

residential use only. If not, replace

 

 

REPRODUCTION

with residential ballast.

 

 

 

Install noise filter in series and close

 

 

 

to problematic device.

 

 

 

Rewire remote module to opposite

 

 

 

power line (L1 or L2) from that of

 

 

 

problematic device.

 

 

6.Communication lost between transfer

6.Contact local authorized service center.

 

 

switch and Symphony II control boards.

 

Generator is still running after

 

1.Minimum engine run time has not elapsed.

1.Wait five minutes for transfer switch to

utility power is restored

 

 

retransfer to utility power.

 

 

2.Fuse(s) in transfer switch is defective.

2.Contact local authorized service center.

NOT

 

Relay modules do not close after 1.Too much load on generator.

1.Decrease load to generator.

five minutes

 

2.Communication interruption.

2.Reset utility disconnect circuit breaker

 

FOR

in transfer switch and wait five

 

 

 

minutes (turn OFF breaker for ten

 

 

 

seconds then turn it back ON).

 

 

3.Priority set to 9 or 10.

3.Appliance will not turn on during

 

 

 

standby power. Contact local

 

 

 

authorized service center to change

 

 

 

priority setting.

Relay modules do not open during Communication interruption.

Contact local authorized service center.

transfer and retransfer

 

 

 

Symphony II system control board 1.TxRx and TxRx GND communication

1.Contact local authorized service center.

status LED does not change

 

wires are not connected between the

 

illumination blinking pattern

 

generator and transfer switch.

 

for utility or generator power.. 2.TxRx and TxRx GND communication wires

2.Contact local authorized service center.

 

 

are connected incorrectly between the

 

 

 

generator and transfer switch.

 

 

 

3.TxRx and TxRx GND communication

3.Contact local authorized service center.

 

 

wires affected by electrical noise

 

 

 

interference.

 