![](/images/new-backgrounds/1027060/2706021x1.webp)
CAP | COLLECTOR BOX DRAIN TUBE (BLUE) |
|
COLLECTOR BOX TUBE (GREEN)
PLUG
COLLECTOR BOX TUBE (PINK)
CONDENSATE |
TRAP |
COLLECTOR BOX DRAIN TUBE |
(BLUE AND WHITE STRIPED) |
INDUCER HOUSING
DRAIN TUBE (VIOLET)
COLLECTOR BOX
EXTENSION TUBE
Fig. 11ÐHorizontal Right Tube Configuration
A93354
5.Route this extended tube (pink label) to condensate trap relief port connection.
6.Determine appropriate length, cut, and connect tube.
7.Clamp tube to relief port connection.
E. Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommenda- tions and procedures.
F.Construct a Working Platform
|
|
|
|
|
|
|
|
| |
LEVEL |
| (0″) | FRONT |
|
|
| |||
|
|
|
| ||||||
|
|
|
| ||||||
|
|
|
| ||||||
TO | LEVEL (0″) | ||||||||
| |||||||||
1⁄2″ MAX |
| TO | |||||||
|
|
|
|
|
| 1⁄2″ MAX | |||
UPFLOW OR DOWNFLOW |
FRONT
HORIZONTAL
Construct working platform where all required furnace clearances are met. (See Fig. 3 and 10.)
CAUTION: The condensate trap MUST be installed below furnace. See Fig. 4 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain.
NOTE:
A93025
NOTE: For proper furnace operation, install furnace so that it is level or pitched forward within 1/2 in. to ensure proper condensate drainage from secondary heat exchangers.
Locate furnace as close to center of air distribution system as possible.
Locate furnace so
NOTE: A
LOCATION
I.GENERAL
When a furnace is installed so that supply ducts carry air to areas outside the space containing the furnace, return air must also be handled by ducts sealed to furnace casing. The ducts terminate outside the space containing the furnace to ensure there will not be a negative pressure condition within equipment room or space. Furnace may be located in a confined space without special provisions for dilution or ventilation air. This furnace must be installed so electrical components are protected from water.
Ð11Ð
CAUTION: If these furnaces are used during construc- tion when adhesives, sealers, and/or new carpets are being installed, make sure all combustion and circulating air requirements are followed. If operation of furnace is required during construction, use clean outside air for combustion and ventilation. Compounds of chlorine and fluorine, when burned with combustion air, form acids which will cause corrosion of heat exchangers. Some of these compounds are found in paneling, dry wall adhe- sives, paints, thinners, masonry cleaning materials, and many other solvents commonly used in the construction process.
Excessive exposure to contaminated combustion air will result in safety and performance related problems.