Bryant 355M-40-5, 355M-40-4 ÐHorizontal Right Tube Configuration, Location General

Models: 355M-40-4 355M-40-5

1 44
Download 44 pages 32.02 Kb
Page 11
Image 11

CAP

COLLECTOR BOX DRAIN TUBE (BLUE)

 

COLLECTOR BOX TUBE (GREEN)

PLUG

COLLECTOR BOX TUBE (PINK)

CONDENSATE

TRAP

COLLECTOR BOX DRAIN TUBE

(BLUE AND WHITE STRIPED)

INDUCER HOUSING

DRAIN TUBE (VIOLET)

COLLECTOR BOX

EXTENSION TUBE

Fig. 11ÐHorizontal Right Tube Configuration

A93354

5.Route this extended tube (pink label) to condensate trap relief port connection.

6.Determine appropriate length, cut, and connect tube.

7.Clamp tube to relief port connection.

E. Condensate Trap Freeze Protection

Refer to Condensate Drain Protection section for recommenda- tions and procedures.

F.Construct a Working Platform

 

 

 

 

 

 

 

 

 

LEVEL

 

(0)

FRONT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO

LEVEL (0)

 

12MAX

 

TO

 

 

 

 

 

 

12MAX

UPFLOW OR DOWNFLOW

FRONT

HORIZONTAL

Construct working platform where all required furnace clearances are met. (See Fig. 3 and 10.)

CAUTION: The condensate trap MUST be installed below furnace. See Fig. 4 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain.

NOTE: Combustion-air and vent pipes are restricted to a mini- mum length of 5 ft. (See Table 6.)

A93025

NOTE: For proper furnace operation, install furnace so that it is level or pitched forward within 1/2 in. to ensure proper condensate drainage from secondary heat exchangers.

Locate furnace as close to center of air distribution system as possible.

Locate furnace so combustion-air pipe lengths are not exceeded. Refer to Table 6.

NOTE: A 12-in. minimum offset pipe section is recommended with short (5 to 8 ft) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. (See Fig. 10 or 29.)

LOCATION

I.GENERAL

When a furnace is installed so that supply ducts carry air to areas outside the space containing the furnace, return air must also be handled by ducts sealed to furnace casing. The ducts terminate outside the space containing the furnace to ensure there will not be a negative pressure condition within equipment room or space. Furnace may be located in a confined space without special provisions for dilution or ventilation air. This furnace must be installed so electrical components are protected from water.

Ð11Ð

CAUTION: If these furnaces are used during construc- tion when adhesives, sealers, and/or new carpets are being installed, make sure all combustion and circulating air requirements are followed. If operation of furnace is required during construction, use clean outside air for combustion and ventilation. Compounds of chlorine and fluorine, when burned with combustion air, form acids which will cause corrosion of heat exchangers. Some of these compounds are found in paneling, dry wall adhe- sives, paints, thinners, masonry cleaning materials, and many other solvents commonly used in the construction process.

Excessive exposure to contaminated combustion air will result in safety and performance related problems.

Page 11
Image 11
Bryant 355M-40-5, 355M-40-4 operating instructions ÐHorizontal Right Tube Configuration, Location General