![](/images/new-backgrounds/1027060/2706081x1.webp)
BURNER
ORIFICE
A93059
CAUTION: DO NOT redrill orifices. Improper drilling (burrs,
BURNER FLAME
BURNER
MANIFOLD
A89020
Fig. 49ÐBurner Flame
At altitudes above 2000 ft, this furnace has been ap- proved for a 2 percent derate for each 1000 ft above sea level. See Table 13 for derate multiplier factor and example.
TABLE 13ÐALTITUDE DERATE MULTIPLIER FOR U.S.A.
ALTITUDE | % OF | DERATE MULTIPLIER |
(FT) | DERATE | FACTOR FOR U.S.A.* |
0Ð2000 | 0 | 1.00 |
2001Ð3000 | 4Ð6 | 0.95 |
3001Ð4000 | 6Ð8 | 0.93 |
4001Ð5000 | 8Ð10 | 0.91 |
5001Ð6000 | 10Ð12 | 0.89 |
6001Ð7000 | 12Ð14 | 0.87 |
7001Ð8000 | 14Ð16 | 0.85 |
8001Ð9000 | 16Ð18 | 0.83 |
9001Ð10,000 | 18Ð20 | 0.81 |
|
|
|
* Derate multiplier factor is based on midpoint altitude for altitude range.
EXAMPLE:
100,000 Btuh input furnace installed at 4300 ft.
Furnace Input |
| Derate |
| Furnace Input Rate |
Rate at | X | Multiplier | = | at Installation |
Sea Level |
| Factor |
| Altitude |
100,000 | X | 0.91 | = | 91,000 |
CANADA
At installation altitudes from 2000 to 4500 ft, this furnace must be derated 5 percent by an authorized Gas Conversion Station or Dealer. To determine correct input rate for altitude, see example above and use 0.95 as derate multiplier factor.
b. Reinstall burner box cover.
NOTE: Clocking gas input rate MUST always be performed with the burner box cover INSTALLED.
c. Check that gas valve adjustment caps are in place for proper input to be clocked.
d. Obtain yearly heat value average for local gas supply.
NOTE: Be sure heating value of gas used for calculations is correct for your altitude. Consult local gas utility for altitude adjustment of gas heating value.
e. Check and verify orifice size in furnace. NEVER AS-
SUME THE ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
f.Turn off all other gas appliances and pilots.
g.Turn setup switch
h.Let furnace run for 3 minutes in
i.Measure time (in sec) for gas meter to complete 1 revolution. Note reading.
j.Refer to Table 14 for cubic ft of gas per hr.
k.Multiply gas rate cu ft/hr by heating value (Btu/cu ft).
l.Turn setup switch
EXAMPLE:
Btu heating input = Btu/cu ft X cu ft/hr Heating value of gas = 975 Btu/cu ft
Time for 1 revolution of
Btu heating input = 103 X 975 = 100,425 Btuh In this example, the orifice size and manifold pressure adjustment is within ±2 percent of the furnace input rate.
NOTE: Measured gas inputs (high heat and low heat) must be within ±2 percent of that stated on furnace rating plate when installed at sea level or derated per that stated above when installed at higher altitudes.
m.Remove jumper across R, W/W1, and W2 thermostat connections to terminate call for heat.
Ð41Ð