Bryant 551C 551B,C, Hood Box Removal, Indoor Coil Access Panel Relocation, Resistance Values

Models: 551B

1 61
Download 61 pages 53.59 Kb
Page 25
Image 25
Fig. 23 ---Hood Box Removal

 

 

 

x

 

 

 

o

 

o

B

 

HOOD BOX

H

od

 

 

 

 

 

BRACKET

 

 

 

 

C06024

Fig. 23 ---Hood Box Removal

SIDE

PANEL

 

 

 

TOP

 

 

 

SIDE

 

 

CAULK

PANEL

 

 

 

 

 

HERE

 

 

INDOOR

 

INDOOR

 

COIL

 

COIL

 

ACCESS

 

ACCESS

 

PANEL

 

PANEL

 

 

 

C06025

Fig. 24 ---Indoor Coil Access Panel Relocation

 

 

 

TOP

 

 

 

PANEL

 

 

 

INDOOR COIL

 

 

 

ACCESS PANEL

LEFT

 

 

 

HOOD

SCREW

 

SIDE

B

 

 

 

19 1/16”

 

 

 

 

 

33 3/8”

 

HOOD DIVIDER

 

 

 

 

C06026

 

Fig. 25 ---Outdoor-Air Hood Construction

EconoMi$er IV Standard Sensors

Outdoor Air Temperature (OAT) Sensor

The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA device used to measure the outdoor-air temperature. The outdoor-air temperature is used to determine when the EconoMi$er IV can be used for free cooling. The sensor is factory-installed on the EconoMi$er IV in the outdoor airstream.

(See Fig. 21.) The operating range of temperature measurement is 40_ to 100_F.

Supply Air Temperature (SAT) Sensor

The supply air temperature sensor is a 3k ohm thermistor located at the inlet of the indoor fan. (See Fig. 32.) This sensor is factory installed. The operating range of temperature measurement is 0° to 158_F. See Table 5 for sensor temperature/resistance values.

Table 5—Supply Air Sensor Temperature/

Resistance Values

TEMPERATURE (F)

 

RESISTANCE (ohms)

 

–58

 

200,250

 

 

–40

 

100,680

 

 

–22

 

53,010

 

 

 

–4

 

29,091

 

14

 

 

16,590

 

32

 

 

9,795

 

 

50

 

 

5,970

 

 

68

 

 

3,747

 

 

77

 

 

3,000

 

 

86

 

 

2,416

 

 

104

 

 

1,597

 

 

122

 

 

1,080

 

 

140

 

 

746

 

 

158

 

 

525

 

 

176

 

 

376

 

 

185

 

 

321

 

 

194

 

 

274

 

 

212

 

 

203

 

 

230

 

 

153

 

 

248

 

 

116

 

 

257

 

 

102

 

 

266

 

 

89

 

 

284

 

 

70

 

 

302

 

 

55

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17 1/4”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIVIDER

OUTSIDEFig. 24 ---Indoor Coil Access Panel RelocationFig. 25 ---Outdoor-Air Hood Construction

EconoMi$er IV Standard SensorsAIR

HOOD

CLEANABLEOutdoor Air Temperature (OAT) SensorSupply Air Temperature (SAT) SensorTable 5—Supply Air Sensor Temperature/ ALUMINUM Resistance Values FILTER

FILTER

BAROMETRIC RELIEF

FILTER CLIP

C06027

Fig. 26 ---Filter Installation

The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.

Outdoor Air Lockout Sensor

The EconoMi$er IV is equipped with an ambient temperature lockout switch located in the outdoor air stream which is used to lockout the compressors below a 42_F ambient temperature. (See Fig. 21.)