Table 22—Fan Performance 551B 072 — Vertical Discharge Units; Standard Motor (Belt Drive)*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

 

0.8

 

 

1.0

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1800

907

0.63

558

1006

0.80

708

1092

0.97

860

 

1169

1.14

1015

1239

1.32

1174

1900

945

0.72

638

1042

0.90

796

1126

1.08

956

 

1201

1.26

1119

1271

1.45

1285

2000

984

0.82

727

1078

1.00

892

1160

1.19

1060

 

1235

1.39

1230

1303

1.58

1403

2100

1024

0.93

823

1115

1.12

997

1195

1.32

1173

 

1268

1.52

1350

1335

1.72

1531

2200

1063

1.05

929

1152

1.25

1111

1230

1.46

1294

 

1302

1.67

1480

1368

1.88

1668

2300

1103

1.18

1044

1189

1.39

1234

1266

1.60

1425

 

1337

1.82

1618

1402

2.04

1814

2400

1143

1.32

1168

1227

1.54

1367

1302

1.76

1566

 

1371

1.99

1767

1435

2.22

1970

2500

1183

1.47

1303

1265

1.70

1510

1339

1.93

1717

 

1406

2.17

1926

2600

1224

1.63

1448

1303

1.87

1663

1375

2.12

1878

 

1442

2.36

2095

2700

1264

1.81

1604

1342

2.06

1828

1412

2.31

2051

 

2800

1305

1.99

1772

1381

2.26

2003

 

2900

1346

2.20

1951

 

3000

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

CFM

 

1.2

 

 

1.4

 

 

1.6

 

 

 

1.8

 

 

2.0

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1800

1304

1.51

1337

1365

1.69

1503

1422

1.88

1674

 

1477

2.08

1848

1528

2.28

2025

1900

1335

1.64

1454

1395

1.83

1627

1452

2.03

1804

 

1506

2.23

1984

2000

1366

1.78

1580

1426

1.98

1760

1482

2.19

1943

 

1535

2.40

2130

2100

1398

1.93

1715

1457

2.14

1901

1512

2.35

2091

 

2200

1430

2.09

1858

1488

2.31

2052

 

2300

1462

2.27

2012

 

2400

 

2500

 

2600

 

2700

 

2800

 

2900

 

3000

 

NOTES:

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

1. Bold cells indicate field-supplied drive is required.

 

 

Bhp — Brake Horsepower

 

 

 

 

2. Maximum continuous bhp is 2.40.

 

 

 

 

Watts — Input Watts to Motor

 

 

 

 

3. See general fan performance notes.

 

 

 

 

*Motor drive range: 1120 to 1585 rpm. All other rpms require field-supplied

 

 

 

 

 

 

 

 

drive.

 

 

 

 

 

 