Table 10—Evaporator-Fan Motor Data — Standard Motor

UNIT

UNIT

MAXIMUM

MAXIMUM

 

MAXIMUM

 

551B

UNIT VOLTAGE

 

PHASE

CONTINUOUS BHP*

OPERATING WATTS*

AMP DRAW

 

551C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

024

ALL

0.58

580

2.0

75.0

 

 

Single

1.20

1000

208/230

4.9

 

036

 

 

 

208/230

4.9

 

Three

1.20

1000

460

2.2

 

 

 

 

 

 

 

575

2.2

 

 

Single

1.20

1000

208/230

4.9

 

048

 

 

 

208/230

4.9

 

Three

1.20

1000

460

2.2

 

 

 

 

 

 

 

575

2.2

 

 

Single

1.30

1455

208/230

7.0

 

060

 

 

 

208/230

6.7

 

Three

2.40

2120

460

3.0

 

 

 

 

 

 

 

575

3.0

 

 

 

 

 

 

072

 

 

 

208/230

6.7

 

Three

2.40

2120

460

3.0

 

 

 

 

 

575

3.0

 

LEGEND

Bhp — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

551B,C

Table 11—Evaporator-Fan Motor Data — High-Static Motors

UNIT

UNIT

MAXIMUM

MAXIMUM

 

MAXIMUM

551B

UNIT VOLTAGE

PHASE

CONTINUOUS BHP*

OPERATING WATTS*

AMP DRAW

551C

 

 

 

 

 

 

 

 

 

 

 

 

036

 

 

 

208/230

6.7

Three

2.40

2120

460

3.0

 

 

 

 

575

3.0

048

 

 

 

208/230

6.7

Three

2.40

2120

460

3.0

 

 

 

 

575

3.0

060

 

 

 

208/230

8.6

Three

2.90

2615

460

3.9

 

 

 

 

575

3.9

072

 

 

 

208/230

8.6

Three

2.90

2615

460

3.9

 

 

 

 

575

3.9

LEGEND

Bhp — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

Table 12—Accessory/FIOP Electric Heaters Static Pressure Drop (in. wg) — 551B 036-072 and 551C 024-060

COMPONENT

 

 

 

 

 

CFM

 

 

 

 

600

900

1200

1400

1600

1800

2000

2200

2400

2600

 

1 Heater Module

0.03

0.05

0.07

0.09

0.09

0.10

0.11

0.11

0.12

0.13

2 Heater Modules

0.14

0.15

0.16

0.16

0.16

0.17

0.17

0.17

0.18

0.18

Table 13—Accessory/FIOP EconoMi$er IV and EconoMi$er2 Static Pressure* (in. wg) — 551B 036-072 and 551C 024-060

COMPONENT

 

 

 

 

 

CFM

 

 

 

 

 

600

800

1000

1250

1500

1750

2000

2250

2500

2750

3000

 

Vertical EconoMi$er IV

0.01

0.02

0.035

0.045

0.065

0.08

0.12

0.145

0.175

0.22

0.255

Horizontal EconoMi$er IV

---

---

---

0.1

0.125

0.15

0.18

0.225

0.275

LEGEND

FIOP --- Factory ---Installed Option

*The static pressure must be added to external static pressure. The sum and the indoor entering-air cfm should be used in conjunction with the Fan Performance tables to determine indoor blower rpm and watts.