Bryant 551C installation instructions 551B,C, Roof Curb Alignment

Models: 551B

1 61
Download 61 pages 53.59 Kb
Page 5
Image 5
Fig. 6 ---

NOTES:

1.

Place unit on curb as close as possible to the duct end.

2.

Dimension in ( ) is in millimeters.

3.Hook rigging shackles through holes in base rail as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.

4.Weights include base unit without economizer. See Table 1 for unit operating weights with accessory economizer.

5.Weights include base unit without the Perfect Humidityt adaptive dehumidification system. See Table 1 for unit operating weights with the Perfect Humidityt system.

C06111

 

 

 

 

Fig. 6 ---

Rigging Details

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

OPERATING

 

 

 

 

DIMENSIONS

 

 

 

 

WEIGHT

“A”

 

 

 

“B”

 

“C”

551C

 

 

 

 

 

lb

 

kg

in.

 

mm

 

in.

 

mm

in.

 

mm

 

 

 

 

 

 

024

435

 

197

73.69

 

1872

 

35.50

 

902

33.31

 

847

036

445

 

202

73.69

 

1872

 

35.50

 

902

33.31

 

847

048

465

 

211

73.69

 

1872

 

35.50

 

902

33.31

 

847

060

520

 

236

73.69

 

1872

 

35.50

 

902

41.31

 

1050

UNIT

OPERATING

 

 

 

 

DIMENSIONS

 

 

 

 

WEIGHT

“A”

 

 

 

“B”

 

“C”

551B

 

 

 

 

 

lb

 

kg

in.

 

mm

 

in.

 

mm

in.

 

mm

 

 

 

 

 

 

036

530

 

240

73.69

 

1872

 

35.50

 

902

33.31

 

847

048

540

 

245

73.69

 

1872

 

35.50

 

902

33.31

 

847

060

560

 

254

73.69

 

1872

 

35.50

 

902

33.31

 

847

072

635

 

288

73.69

 

1872

 

35.50

 

902

41.31

 

1050

! WARNING

PERSONAL INJURY AND PROPERTY DAMAGE

HAZARD

Failure to follow this warning could result in personal injury, death and property damage.

All panels must be in place when rigging and lifting.

551B,C

C06208

Fig. 7 ---Roof Curb Alignment

5

Page 5
Image 5
Bryant 551C installation instructions 551B,C, Roof Curb Alignment