Cooling
Set the space thermostat to the OFF position. Set the system selector switch at COOL position and the fan switch at AUTO position. Adjust the thermostat to a setting below room temperature. The compressor starts when contactor closes.
Check cooling effects at a setting below room temperature. Check the unit charge. Refer to Refrigerant Charge section.
Reset the thermostat at a position above room temperature. The compressor will shut off.
TO SHUT OFF UNIT - Set the system selector switch at OFF position. Resetting the thermostat at a position above room temperature shuts off the unit temporarily until the space temperature exceeds the thermostat setting. Units are equipped with a
Compressor restart is accomplished by manual reset at the thermostat by turning the selector switch to OFF position and then to ON position.
Heating
To start unit, turn on main power supply.
Set system selector switch at HEAT position and set thermostat at a setting above room temperature. Set fan at AUTO position.
First stage of thermostat energizes the
If electric heaters do not energize, reset limit switch (located on
TO SHUT OFF UNIT - Set system selector switch at OFF position. Resetting thermostat at a position below room temperature temporarily shuts unit off until space temperature falls below thermostat setting.
Safety Relief
A soft solder joint at the suction line fitting provides pressure relief under abnormal temperature and pressure conditions.
Ventilation (Continuous Fan)
Set fan and system selector switches at ON and OFF positions, respectively. Evaporator fan operates continuously to provide constant air circulation.
Operating Sequence
Cooling - Units Without Economizer
When thermostat calls for cooling, terminals G and Y1 are energized. The
Heating - Units Without Economizer
When the thermostat calls for heating, terminal W1 will be energized with 24v. The IFC and heater contactor no. 1 (HC1) are energized.
Cooling - Units With EconoMi$er IV
When free cooling is not available, the compressors will be controlled by the zone thermostat. When free cooling is available, the
Integrated EconoMi$er IV operation on
For EconoMi$er IV operation, there must be a thermostat call for the fan (G). This will move the damper to its minimum position during the occupied mode.
If the increase in cooling capacity causes the
If optional power exhaust is installed, as the
If
Damper movement from full closed to full open (or vice versa) will take between
If free cooling can be used as determined from the appropriate changeover command (switch, dry bulb, enthalpy curve, differential dry bulb, or differential enthalpy), a call for cooling (Y1 closes at the thermostat) will cause the control to modulate the dampers open to maintain the supply air temperature set point at 50_ to 55_F.
As the supply air temperature drops below the set point range of 50_ to 55_F, the control will modulate the
Heating - Units With EconoMi$er IV
When the room temperature calls for heat, the heating controls are energized as described in the Heating, Units Without Economizer section. During the occupied mode, whenever the indoor fan contactor is energized, the economizer damper moves to the minimum position.
Units With Perfect Humidity™ Adaptive Dehumidification
System
Normal Design Operation
When the rooftop operates under the normal sequence of operation, the compressors will cycle to maintain indoor conditions. (See Fig. 42.)
The Perfect Humidity adaptive dehumidification system includes a
Subcooling Mode
When subcooling mode is initiated, this will energize (close) the liquid line solenoid valve (LLSV) forcing the hot liquid refrigerant to enter into the subcooling coil. (See Fig. 43.)
As the hot liquid refrigerant passes through the subcooling/ reheat dehumidification coil, it is exposed to the cold supply airflow coming through the evaporator coil. The liquid is further subcooled to a temperature approaching the evaporator
551B,C
49