551B,C
EconoMi$er IV Control Modes |
|
|
|
|
|
| Outdoor Dry Bulb Changeover | ||
Determine the EconoMi$er IV control mode before set up of the | The standard controller is shipped from the factory configured for | ||||||||
control. Some modes of operation may require different | outdoor dry bulb changeover control. The | ||||||||
sensors. (See Table 6.) The EconoMi$er IV is supplied from the | |||||||||
factory with a | control mode, the outdoor temperature is compared to an | ||||||||
temperature sensor. This allows for operation of the EconoMi$er | adjustable set point selected on the control. If the | ||||||||
IV with outdoor air dry bulb changeover control. Additional | temperature is above the set point, the EconoMi$er IV will adjust | ||||||||
accessories can be added to allow for different types of | the | ||||||||
changeover control and operation of the EconoMi$er IV and unit. | temperature is below the set point, the position of the outdoor air | ||||||||
|
|
|
|
|
|
|
|
| dampers will be controlled to provide free cooling using outdoor |
Table | air. When in this mode, the LED next to the free cooling set point | ||||||||
|
|
|
|
|
|
|
|
| potentiometer will be on. The changeover temperature set point is |
|
|
|
|
|
|
|
|
| controlled by the free cooling set point potentiometer located on |
| ECONOMI$ER IV WITH OUTDOOR AIR |
|
| ||||||
|
| the control. (See Fig. 33.) The scale on the potentiometer is A, B, | |||||||
APPLICATION |
| DRY BULB SENSOR |
| ||||||
|
| Accessories Required |
|
| C, and D. See Fig. 34 for the corresponding temperature | ||||
Outdoor Air | None. The outdoor air dry bulb sensor |
|
| changeover values. | |||||
Dry Bulb |
| is factory installed. |
| Differential Dry Bulb Control | |||||
Differential |
| CRTEMPSN002A00* |
|
| |||||
|
|
|
| ||||||
Dry Bulb |
|
| For differential dry bulb control the standard outdoor dry bulb | ||||||
|
|
|
|
|
|
|
| ||
Single Enthalpy |
|
| HH57AC078 |
|
| sensor is used in conjunction with an additional accessory dry | |||
|
|
| HH57AC078 |
|
| ||||
Differential |
|
|
| bulb sensor (part number CRTEMPSN002A00). The accessory | |||||
|
|
|
| and |
|
| |||
Enthalpy |
|
|
|
|
| sensor must be mounted in the return airstream. (See Fig. 35.) | |||
| CRENTDIF004A00* |
|
| ||||||
|
|
| Wiring is provided in the EconoMi$er IV wiring harness. (See | ||||||
CO2 for DCV |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| Fig. 27.) | |
Control using a |
| 33ZCSENCO2 |
|
| |||||
|
| In this mode of operation, the | |||||||
|
|
|
|
|
|
|
| ||
CO2 Sensor |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| compared to the | |
CO2 for DCV | 33ZCSENCO2† |
| O |
|
|
|
| ||
Control using a | and |
|
|
| CRCBDIOX005A00†† |
|
| airstream is used for cooling. When using this mode of | |
|
|
|
|
| |||||
33ZCASPCO2** |
| R |
|
|
|
| changeover control, turn the enthalpy setpoint potentiometer fully | ||
CO2 Sensor |
|
|
|
|
| ||||
|
|
|
|
|
| clockwise to the D setting. (See Fig. 33.) | |||
|
|
|
|
|
|
|
|
|
*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units. As such, these kits may contain parts that will not be needed for installation.
2sensor.
**33ZCASPCO2 is an accessory aspirator box required for
††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZCASPCO2 accessories.
FOR OCCUPANCY CONTROL
REPLACE JUMPER WITH
8
7
LEGEND | Potentiometer Defaults Settings: | ||
DCV— Demand Controlled Ventilation | Power Exhaust | Middle | |
Minimum Pos. | Fully Closed | ||
IAQ — Indoor Air Quality | |||
DCV Max. | Middle | ||
LA — Low Ambient Lockout Device | |||
DCV Set | Middle | ||
OAT — | |||
Enthalpy | C Setting | ||
POT — Potentiometer | |||
|
|
RAT —
NOTES:
1.620 ohm, 1 watt 5% resistor should be removed only when using differential enthalpy or dry bulb.
2.If a separate
3.For
C06028
Fig. 27 --- EconoMi$er IV Wiring
26