3. Provide Combustion Air
INSUFFICIENT COMBUSTION AIR SUPPLY may result in the production and
release of deadly carbon monoxide (CO) into the home which can cause severe personal injury or death.
Like all
Provide combustion air using the instructions in Appendix
4. Connect Venting
IMPROPER VENTING may result in property damage and the release of flue
gases which contain deadly carbon monoxide (CO) into the home, which can cause severe personal injury, death or substantial property damage.
The vent system shall be designed and constructed in accordance with NFPA 54 and applicable local codes to develop a positive flow adequate to convey flue or vent gases to the outdoors, while ensuring that flue gases do not cool prematurely.
Observe all general venting guidelines provided in Appendix
1.This appliance shall be vented into a listed gas vent, masonry, metal, or factory- built chimney as required by NFPA 54 and applicable local codes for Category I appliances. If venting this appliance into a masonry chimney, the chimney must be lined with a listed chimney lining system
(i.e. Type B gas vent or flexible metal) as required by NFPA 54 and applicable local codes. Clay flue lined masonry chimneys do not meet the venting requirements for this appliance.
2.Attach the vent damper with three sheetmetal screws around the perimeter of the flue collar (Figure
3.Vent connector shall be
DAMPER MUST BE OPEN when the main burner is firing.