8. Program the Controls
Using IQ Boiler Control Display
The IQ Boiler Control is located inside the boiler front door, just above the IQ Option Panel (Figure
IQ Boiler Control |
IQ Option Panel |
The IQ Boiler Control display, along with Up ñ, Down ò, and “I” keys may be used to view boiler operating status (Figure
|
| ñ |
I | 1 | ò |
|
IQ Boiler Control
Viewing the Operating Mode Options
In operating mode the user may view (but not change) boiler operating status, settings and troubleshooting information. To view IQ Boiler Control display information:
1. Press and release the “I” key on the IQ Boiler Control to change from one parameter to the next. Each setting will alternately flash between the relevant display code and its corresponding value.
Operating Mode Options
StA Status
bt Boiler Temperature
SP Operating Setpoint (Outdoor Reset)
HL High Limit Setting
HdF High Limit Differential hr Heat Request Status FLA Flame Current
rUn Run Time Hours CYC Boiler Cycles
Err Error (see Error Numbers)
Status Code Displayed in STA Mode
1Standby:
Either TT Open or TT Closed and Boiler Temperature within Setpoint & Differential with circulator running.
4Prepurge
6Spark
7Flame Proving
8Running
10 Retry/Recycle Delay
13 Soft Lockout
14 Hard Lockout
15 Waiting for Limit to Close
16 Flame Present Out of Sequence
17 Self Test
18 Waiting for Damper to Open
19 Waiting for Damper to Close
20 Damper Failure to Open
21 Damper Failure to Close
For example, when the “I” key is pressed on the IQ Boiler Control until “bt” is displayed, it will then flash a three digit number (such as “180”) followed by either “F” (or “C”). This indicates that the boiler water temperature is 180°F. Other operating parameters display the information in a similar fashion.
13