Burnham Series 2B manual Equivalent Length of Fittings, Boiler Piping

Models: Series 2B

1 52
Download 52 pages 42.24 Kb
Page 6
Image 6

Table 1: Maximum Capacity of Schedule 40 Pipe in CFH For Natural Gas Pressures of ½ psig or Less

Length

 

0.3 Inch w.c. Pressure Drop

 

 

0.5 Inch w.c. Pressure Drop

 

 

 

 

 

 

 

 

 

 

 

 

 

[Feet]

½

 

¾

1

 

½

 

¾

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

132

 

278

520

 

1,050

175

 

360

680

 

1,400

 

 

 

 

 

 

 

 

 

 

 

 

 

20

92

 

190

350

 

730

120

 

250

465

 

950

 

 

 

 

 

 

 

 

 

 

 

 

 

30

73

 

152

285

 

590

97

 

200

375

 

770

 

 

 

 

 

 

 

 

 

 

 

 

 

40

63

 

130

245

 

500

82

 

170

320

 

660

 

 

 

 

 

 

 

 

 

 

 

 

 

50

56

 

115

215

 

440

73

 

151

285

 

580

60

50

 

105

195

 

400

66

 

138

260

 

530

70

46

 

96

180

 

370

61

 

125

240

 

490

80

43

 

90

170

 

350

57

 

118

220

 

460

 

 

 

 

 

 

 

 

 

 

 

 

 

90

40

 

84

160

 

320

53

 

110

205

 

430

 

 

 

 

 

 

 

 

 

 

 

 

 

100

38

 

79

150

 

305

50

 

103

195

 

400

Table 2: Equivalent Length of Fittings

Fitting

 

Nominal Pipe Size

 

 

 

 

 

 

 

½

 

¾

1

 

 

 

 

 

 

 

 

 

 

 

45° Ell

0.7

 

1

1.2

 

1.6

 

 

 

 

 

 

 

90° Ell

1.6

 

2.1

2.6

 

3.5

 

 

 

 

 

 

 

Tee (As Elbow)

3.1

 

4.1

5.2

 

6.9

 

 

 

 

 

 

 

This piping is to be supplied by the installer and must include a trap, a ground joint union and a manual shutoff valve upstream of the gas control assembly outside of the jacket when codes require, see Figure 1. A pipe thread compound resistant to the action of liquefied petroleum gases should be applied to all threaded joints in the gas piping. Pressure testing of the Gas Supply Piping Boiler and its connections is required before placing the boiler in operation.

The boiler and shutoff valve must be disconnected from the gas supply piping system during any pressure testing at pressures greater than ½ psig (3.5kPa).

The boiler must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at pressures equal to or less than ½ psig (3.5kPa).

Recommended sizing of gas supply piping to boiler for natural gas - shall be such as to provide the required supply of gas without undue loss of pressure between meter and the boiler. Gas supply piping should be sized in accordance with the Tables 1, 2 and 3. The following shall be taken into account:

Table 3: Specific Gravity Correction Factors for Natural Gas

Specific

Correction

Specific

Correction

Gravity

Factor

Gravity

Factor

0.50

1.10

1.30

1.07

0.55

1.04

1.40

1.04

0.60

1.00

1.50

1.00

0.65

0.96

1.60

0.97

0.70

0.93

1.70

0.94

0.75

0.90

---

---

0.80

0.87

---

---

A.Allowable loss of pressure to assure a burner manifold pressure of 3½" (8.9cm) water for natural gas.

B.Supply of gas to be provided in cubic feet.

C.Length of piping and number of fittings.

D.Specific gravity of gas.

E.Correction factor for specific gravity.

9.BOILER PIPING

CAUTION

Failure to properly pipe boiler may result in improper operation and damage to boiler or building.

A.Clearances - Hot water pipes do not require clearance from combustible construction.

B.Install drain valve and safety relief valve as shown in Figures 1 and 3. Note - Safety relief valve must be in vertical position.

C.Pipe safety relief valve discharge to floor.



Page 6
Image 6
Burnham Series 2B manual Equivalent Length of Fittings, Specific Gravity Correction Factors for Natural Gas, Boiler Piping