![](/images/backgrounds/107718/107718-487x1.png)
GN5060, GN6575
Troubleshooting ChartSymptom | Possible Cause(s) | Corrective Action | ||
|
|
|
|
|
Engine will not | 1. | Run switch is set to "OFF". | 1. | Set run switch to "ON". |
start | 2. | Fuel valve is turned to "CLOSE". | 2. | Turn fuel valve to "OPEN" position. |
| 3. | Choke is open. | 3. | Close the choke. |
| 4. | Fuel tank is empty. | 4. | Add gas. |
| 5. | Engine is filled with | 5. | Change the gas in the engine. |
|
| contaminated or old gas | 6. | Clean spark plug. |
| 6. | Spark plug is dirty. | ||
| 7. | Spark plug is broken. | 7. | Replace spark plug. |
| 8. | Unit is not on level surface. | 8. | Move unit to a level surface to prevent low oil shutdown from |
|
|
|
| triggering. |
| 9. | Oil is low. | 9. | Add or replace oil. |
Engine runs | 1. | Main or secondary circuit | 1. | Reset main or secondary circuit breaker(s). |
but there is no |
| breaker(s) are tripped. |
|
|
electrical output | 2. | Bad connecting of wires/cables. | 2. | If you are using an extension cord, try a different one. |
| 3. | Bad electrical device connected | 3. | Try connecting a different device. |
|
| to generator. |
|
|
Generator runs | 1. | Generator is overloaded | 1. | Turn off all electrical devices. Unplug all electrical devices. Turn |
but does not |
|
|
| off generator. Wait several minutes. Restart generator. Try |
support all |
|
|
| connecting fewer electrical loads to the generator. |
electrical devices | 2. | Short in one of the connected | 2. | Try disconnecting any faulty or |
connected. |
| devices. |
|
|
| 3. | Air cleaner is dirty. | 3. | Clean or replace air cleaner. |
No output | 1. | Engine speed is too slow | 1. | Adjust engine speed. ★ |
voltage | 2. | Open, shorted, or incorrect | 2. | Referring to the wiring diagram, clean and reconnect all |
|
| wiring |
| wiring. ★ |
| 3. | Faulty capacitor | 3. | Replace capacitor. ★ |
| 4. | Open or shorted field windings | 4. | Test winding resistance, replace field winding if necessary. ★ |
| 5. | Open diodes | 5. | Test diodes, replace if necessary. ★ |
| 6. | Circuit breaker tripped | 6. | Reset circuit breaker. |
Low output | 1. | Engine speed is too slow | 1. | Adjust engine speed. ★ |
voltage with no | 2. | Open diodes | 2. | Test diodes, replace if necessary. ★ |
load | 3. | Faulty capacitor | 3. | Replace capacitor. ★ |
| 4. | Open or shorted field windings | 4. | Test winding resistance, replace field winding if necessary. ★ |
High output | 1. | Faulty capacitor | 1. | Replace capacitor. ★ |
voltage with no | 2. | Engine speed is too fast | 2. | Adjust engine speed. ★ |
load |
|
|
|
|
Low output | 1. | Open diode | 1. | Test diodes, replace if necessary. ★ |
voltage under | 2. | Engine speed too slow at full | 2. | Adjust engine speed. ★ |
load |
| load | 3. | Reduce the applied load. |
| 3. | Excessive load applied |
|
|
Erratic output | 1. | Unbalanced engine | 1. | Refer to engine manual. |
voltage | 2. | Dirty, corroded, or loose wiring | 2. | Referring to the wiring diagram, clean and reconnect all |
|
| connection |
| wiring. ★ |
| 3. | Unstable load applied | 3. | Remove all loads, then apply each one individually to |
|
|
|
| determine which one is causing erratic function. |
Noisy operation | 1. | Loose generator or engine bolt | 1. | Tighten all mountings. |
| 2. | Short circuit in generator field or | 2. | Test winding resistance, replace field winding if necessary. ★ |
|
| load |
| Test load devices for shorts. Replace defective load device. |
| 3. | Faulty bearing | 3. | Replace bearing. |
1. | Damaged or disconnect wire in | 1. | Repair or replace wiring. | |
not work |
| idle control circuit. |
|
|
| 2. | Failed idle control circuit board. | 2. | Replace idle control board. |
| 3. | Failed current sensing coil. | 3. | Replace current sensing coil. |
★These diagnostic and repair procedures should be performed by an authorized service center.
www.chpower.com
7